3 HARDWARE

3.3L90 CHANNEL COMMUNICATION

The L90 relay requires a special communications module which is plugged into slot "W" for horizontal-mounting units or slot
"R" for vertical-mounting units. This module is available in several varieties. Relay-to-relay channel communication is not
the same as the 10Base-F interface (available as an option with the CPU module). Channel communication is used for
sharing data among relays.
Table 3–3: CHANNEL COMMUNICATION OPTIONS
MODULE
SPECIFICATION
2A
C37.94SM, 1300 nm, single-mode, ELED, 1 channel single-mode
2B
C37.94SM, 1300 nm, single-mode, ELED, 2 channel single-mode
7A
820 nm, multi-mode, LED, 1 channel
7B
1300 nm, multi-mode, LED, 1 channel
7C
1300 nm, single-mode, ELED, 1 channel
7D
1300 nm, single-mode, LASER, 1 channel
7E
Channel 1: G.703, Channel 2: 820 nm, multi-mode
7F
Channel 1: G.703, Channel 2: 1300 nm, multi-mode
7G
Channel 1: G.703, Channel 2: 1300 nm, single-mode ELED
7H
820 nm, multi-mode, LED, 2 channels
7I
1300 nm, multi-mode, LED, 2 channels
7J
1300 nm, single-mode, ELED, 2 channels
7K
1300 nm, single-mode, LASER, 2 channels
7L
Channel 1: RS422, Channel: 820 nm, multi-mode, LED
7M
Channel 1: RS422, Channel 2: 1300 nm, multi-mode, LED
7N
Channel 1: RS422, Channel 2: 1300 nm, single-mode, ELED
7P
Channel 1: RS422, Channel 2: 1300 nm, single-mode, LASER
7Q
Channel 1: G.703, Channel 2: 1300 nm, single-mode, LASER
7R
G.703, 1 channel
7S
G.703, 2 channels
7T
RS422, 1 channel
7W
RS422, 2 channels
72
1550 nm, single-mode, LASER, 1 channel
73
1550 nm, single-mode, LASER, 2 channels
74
Channel 1 - RS422; Channel 2 - 1550 nm, single-mode, LASER
75
Channel 1 - G.703; Channel 2 - 1550 nm, single-mode, LASER
76
IEEE C37.94, 820 nm, multi-mode, LED, 1 channel
77
IEEE C37.94, 820 nm, multi-mode, LED, 2 channels
The above table shows the various channel communication interfaces available for the L90 relay. All of the fiber modules
use ST type connectors. For two-terminal applications, each L90 relay requires at least one communications channel.
The current differential function must be "Enabled" for the communications module to work. Refer to
!"
TINGS
GROUPED ELEMENTS
NOTE
The fiber optic modules (7A to 7W) are designed for back-to-back connections of L90 relays only. For con-
nections to higher-order systems, use the 72 to 77 modules or the 2A/2B modules.