APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 22 of 41)
ADDR
REGISTER NAME
Load Encroachment (Read/Write Grouped Setting)
6700
Load Encroachment Function
6701
Load Encroachment Source
6702
Load Encroachment Minimum Voltage
6703
Load Encroachment Reach
6704
Load Encroachment Angle
6705
Load Encroachment Pickup Delay
6706
Load Encroachment Reset Delay
6707
Load Encroachment Block
6708
Load Encroachment Target
6709
Load Encroachment Events
670A
Load Encroachment Reserved (6 items)
Autoreclose 1P 3P (Read/Write Setting)
6890
Autoreclose Mode
6891
Autoreclose Maximum Number of Shots
6892
Autoreclose Block Breaker 1
6893
Autoreclose Close Time Breaker 1
6894
Autoreclose Breaker Manual Close
6895
Autoreclose Function
6896
Autoreclose Block Time Manual Close
6897
Autoreclose 1P Initiate
6898
Autoreclose 3P Initiate
6899
Autoreclose 3P TD Initiate
689A
Autoreclose Multi-Phase Fault
689B
Autoreclose Breaker 1 Pole Open
689C
Autoreclose Breaker 3 Pole Open
689D
Autoreclose 3-Pole Dead Time 1
689E
Autoreclose 3-Pole Dead Time 2
689F
Autoreclose Extend Dead T1
68A0
Autoreclose Dead T1 Extension
68A1
Autoreclose Reset
68A2
Autoreclose Reset Time
68A3
Autoreclose Breaker Closed
68A4
Autoreclose Block
68A5
Autoreclose Pause
68A6
Autoreclose Incomplete Sequence Time
68A7
Autoreclose Block Breaker 2
68A8
Autoreclose Close Time Breaker 2
68A9
Autoreclose Transfer 1 to 2
68AA
Autoreclose Transfer 2 to 1
68AB
Autoreclose Breaker 1 Fail Option
68AC
Autoreclose Breaker 2 Fail Option
68AD
Autoreclose 1P Dead Time
68AE
Autoreclose Breaker Sequence
68AF
Autoreclose Transfer Time
68B0
Autoreclose Event
68B1
Autoreclose 3P Dead Time 3
68B2
Autoreclose 3P Dead Time 4
68B3
Reserved (14 items)
Phase Undervoltage (Read/Write Grouped Setting) (2 modules)
7000
Phase UV1 Function
7001
Phase UV1 Signal Source
7002
Phase UV1 Pickup
7003
Phase UV1 Curve
GE Multilin
RANGE
0 to 1
0 to 5
0 to 3
0.02 to 250
5 to 50
0 to 65.535
0 to 65.535
0 to 65535
0 to 2
0 to 1
0 to 65535
0 to 3
1 to 4
0 to 65535
0 to 655.35
0 to 65535
0 to 1
0 to 655.35
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 655.35
0 to 655.35
0 to 65535
0 to 655.35
0 to 65535
0 to 655.35
0 to 65535
0 to 65535
0 to 65535
0 to 655.35
0 to 65535
0 to 655.35
0 to 1
0 to 1
0 to 1
0 to 1
0 to 655.35
0 to 4
0 to 655.35
0 to 1
0 to 655.35
0 to 655.35
---
0 to 1
0 to 5
0 to 3
0 to 1
L90 Line Differential Relay
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F102
---
1
F167
pu
0.001
F001
ohms
0.01
F001
degrees
1
F001
s
0.001
F001
s
0.001
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F080
---
1
F001
---
1
F300
s
0.01
F001
---
1
F300
---
1
F102
s
0.01
F001
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
s
0.01
F001
s
0.01
F001
---
1
F300
s
0.01
F001
---
1
F300
s
0.01
F001
---
1
F300
---
1
F300
---
1
F300
s
0.01
F001
---
1
F300
s
0.01
F001
---
1
F126
---
1
F126
---
1
F081
---
1
F081
s
0.01
F001
---
1
F082
s
0.01
F001
---
1
F102
s
0.01
F001
s
0.01
F001
---
---
F001
---
1
F102
---
1
F167
pu
0.001
F001
---
1
F111
DEFAULT
0 (Disabled)
0 (SRC 1)
250
100
B
30
0
0
0
0 (Self-reset)
0 (Disabled)
0
0 (1 & 3 Pole)
2
0
10
0
0 (Disabled)
1000
0
0
0
0
0
0
50
120
0
50
0
6000
0
0
0
500
0
10
0 (No)
0 (No)
0 (Continue)
0 (Continue)
100
3 (1 - 2)
400
0 (Disabled)
200
400
0
0 (Disabled)
0 (SRC 1)
1000
0 (Definite Time)
B-29