APPENDIX B
[56] ACTIVE SETTING GROUP (1 to 6)
[62] MISCELLANEOUS EVENTS (see F146 for range)
[64 to 127] ELEMENT STATES
F400
UR_UINT16: CT/VT BANK SELECTION
bitmask
bank selection
0
Card 1 Contact 1 to 4
1
Card 1 Contact 5 to 8
2
Card 2 Contact 1 to 4
3
Card 2 Contact 5 to 8
4
Card 3 Contact 1 to 4
5
Card 3 Contact 5 to 8
F500
UR_UINT16: PACKED BITFIELD
First register indicates input/output state with bits 0(MSB)-15(LSB)
corresponding to input/output state 1-16. The second register indi-
cates input/output state with bits 0-15 corresponding to input/out-
put state 17-32 (if required) The third register indicates input/
output state with bits 0-15 corresponding to input/output state 33-
48 (if required). The fourth register indicates input/output state with
bits 0-15 corresponding to input/output state 49-64 (if required).
The number of registers required is determined by the specific
data item. A bit value of 0 = Off, 1 = On
F501
UR_UINT16: LED STATUS
Low byte of register indicates LED status with bit 0 representing
the top LED and bit 7 the bottom LED. A bit value of 1 indicates
the LED is on, 0 indicates the LED is off.
F502
BITFIELD: ELEMENT OPERATE STATES
Each bit contains the operate state for an element. See the F124
format code for a list of element IDs. The operate bit for element ID
X is bit [X mod 16] in register [X/16].
GE Multilin
F504
BITFIELD: 3-PHASE ELEMENT STATE
bitmask
element state
0
Pickup
1
Operate
2
Pickup Phase A
3
Pickup Phase B
4
Pickup Phase C
5
Operate Phase A
6
Operate Phase B
7
Operate Phase C
F505
BITFIELD: CONTACT OUTPUT STATE
0 = Contact State, 1 = Voltage Detected, 2 = Current Detected
F506|
BITFIELD: 1 PHASE ELEMENT STATE
0 = Pickup, 1 = Operate
F507
BITFIELD: COUNTER ELEMENT STATE
0 = Count Greater Than, 1 = Count Equal To, 2 = Count Less Than
F508
BITFIELD: DISTANCE ELEMENT STATE
bitmask
distance element state
0
Pickup
1
Operate
2
Pickup AB
3
Pickup BC
4
Pickup CA
5
Operate AB
6
Operate BC
7
Operate CA
8
Timed
9
Operate IAB
10
Operate IBC
11
Operate ICA
F509
BITFIELD: SIMPLE ELEMENT STATE
0 = Operate
F510
BITFIELD: 87L ELEMENT STATE
bitmask
87L Element State
0
Operate A
1
Operate B
L90 Line Differential Relay