APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 20 of 41)
ADDR
REGISTER NAME
Current Differential 87L (Read/Write Grouped Setting)
6000
87L Current Differential Function
6001
87L Current Differential Block
6002
87L Current Differential Signal Source 1
6003
87L Minimum Phase Current Sensitivity
6004
87L Current Differential Tap Setting
6005
87L Current Differential Phase Percent Restraint 1
6006
87L Current Differential Phase Percent Restraint 2
6007
87L Current Differential Phase Dual Slope Breakpoint
600C
87L Current Differential Key DTT
600D
87L Current Differential External Key DTT
600E
87L Current Differential Target
600F
87L Current Differential Event
6010
87L Current Differential Tap 2 Setting
6011
87L Current Differential Signal Source 2
6012
87L Current Differential Signal Source 3
6014
87L Current Differential Signal Source 4
Open Pole Detect (Read/Write Grouped Setting)
6040
Open Pole Detect Function
6041
Open Pole Detect Block
6042
Open Pole Detect A Aux Co
6043
Open Pole Detect B Aux Co
6044
Open Pole Detect C Aux Co
6045
Open Pole Detect Current Source
6046
Open Pole Detect Current Pickup
6047
Open Pole Detect Voltage Source
6048
Open Pole Detect Voltage Input
6049
Open Pole Detect Pickup Delay
604A
Open Pole Detect Reset Delay
604B
Open Pole Detect Target
604C
Open Pole Detect Events
604D
Open Pole Detect Broken Co
CT Failure Detector (Read/Write Setting)
6120
CT Fail Function
6121
CT Fail Block
6122
CT Fail Current Source 1
6123
CT Fail Current Pickup 1
6124
CT Fail Current Source 2
6125
CT Fail Current Pickup 2
6126
CT Fail Voltage Source
6127
CT Fail Voltage Pickup
6128
CT Fail Pickup Delay
6129
CT Fail Target
612A
CT Fail Events
Continuous Monitor (Read/Write Setting)
6130
Continuous Monitor Function
6131
Continuous Monitor I OP
6132
Continuous Monitor I Supervision
6133
Continuous Monitor V OP
6134
Continuous Monitor V Supervision
6135
Continuous Monitor Target
6136
Continuous Monitor Events
Negative Sequence Time Overcurrent (Read/Write Grouped Setting) (2 modules)
6300
Negative Sequence TOC1 Function
GE Multilin
RANGE
0 to 1
0 to 65535
0 to 5
0.1 to 4
0.2 to 5
1 to 50
1 to 70
0 to 20
0 to 1
0 to 65535
0 to 2
0 to 1
0.2 to 5
0 to 6
0 to 6
0 to 6
0 to 1
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 5
0.05 to 20
0 to 5
0 to 1
0 to 65.535
0 to 65.535
0 to 2
0 to 1
0 to 1
0 to 1
0 to 65535
0 to 5
0 to 2
0 to 5
0 to 2
0 to 5
0 to 2
0 to 65.535
0 to 2
0 to 1
0 to 1
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 2
0 to 1
0 to 1
L90 Line Differential Relay
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F102
---
1
F300
---
1
F167
pu
0.01
F001
---
0.01
F001
%
1
F001
%
1
F001
pu
0.1
F001
---
1
F102
---
1
F300
---
1
F109
---
1
F102
---
0.01
F001
---
1
F211
---
1
F211
---
1
F211
---
1
F102
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F167
pu
0.01
F001
---
1
F167
---
1
F102
s
0.001
F001
s
0.001
F001
---
1
F109
---
1
F102
---
1
F102
---
1
F102
---
1
F300
---
1
F167
pu
0.1
F001
---
1
F167
pu
0.1
F001
---
1
F167
pu
0.01
F001
s
0.001
F001
---
1
F109
---
1
F102
---
1
F102
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F109
---
1
F102
---
1
F102
DEFAULT
0 (Disabled)
0
0 (SRC 1)
20
B
100
30
50
10
1 (Enabled)
0
0 (Self-reset)
0 (Disabled)
100
0 (None)
0 (None)
0 (None)
0 (Disabled)
0
0
0
0
0 (SRC 1)
20
0 (SRC 1)
0 (Disabled)
60
100
0 (Self-reset)
0 (Disabled)
0 (Disabled)
0 (Disabled)
0
0 (SRC 1)
2
1 (SRC 2)
2
0 (SRC 1)
20
1000
0 (Self-reset)
0 (Disabled)
0 (Disabled)
0
0
0
0
0 (Self-reset)
0 (Disabled)
0 (Disabled)
B-27