GE L90 Instruction Manual page 416

Line differential relay ur series
Hide thumbs Also See for L90:
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 31 of 41)
ADDR
REGISTER NAME
A412
Selector 1 Timeout
A413
Selector 1 Step Up
A414
Selector 1 Step Mode
A415
Selector 1 Acknowledge
A416
Selector 1 Bit0
B
A417
Selector 1 Bit1
A418
Selector 1 Bit2
A419
Selector 1 Bit Mode
A41A
Selector 1 Bit Acknowledge
A41B
Selector 1 Power Up Mode
A41C
Selector 1 Target
A41D
Selector 1 Events
A41E
Selector 1 Reserved (10 items)
A428
...Repeated for module number 2
Flexcurves C and D (Read/Write Setting)
AC00
FlexCurve C (120 items)
AC78
FlexCurve D (120 items)
Non Volatile Latches (Read/Write Setting) (16 modules)
AD00
Latch 1 Function
AD01
Latch 1 Type
AD02
Latch 1 Set
AD03
Latch 1 Reset
AD04
Latch 1 Target
AD05
Latch 1 Events
AD06
Latch 1 Reserved (4 items)
AD0A
...Repeated for module number 2
AD14
...Repeated for module number 3
AD1E
...Repeated for module number 4
AD28
...Repeated for module number 5
AD32
...Repeated for module number 6
AD3C
...Repeated for module number 7
AD46
...Repeated for module number 8
AD50
...Repeated for module number 9
AD5A
...Repeated for module number 10
AD64
...Repeated for module number 11
AD6E
...Repeated for module number 12
AD78
...Repeated for module number 13
AD82
...Repeated for module number 14
AD8C
...Repeated for module number 15
AD96
...Repeated for module number 16
Digital Elements (Read/Write Setting) (16 modules)
B000
Digital Element 1 Function
B001
Digital Element 1 Name
B015
Digital Element 1 Input
B016
Digital Element 1 Pickup Delay
B018
Digital Element 1 Reset Delay
B01A
Digital Element 1 Block
B01B
Digital Element 1 Target
B01C
Digital Element 1 Events
B01D
Digital Element 1 Reserved (3 items)
B020
...Repeated for module number 2
B040
...Repeated for module number 3
B060
...Repeated for module number 4
B080
...Repeated for module number 5
B-38
RANGE
3 to 60
0 to 65535
0 to 1
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 1
0 to 65535
0 to 2
0 to 2
0 to 1
---
0 to 65535
0 to 65535
0 to 1
0 to 1
0 to 65535
0 to 65535
0 to 2
0 to 1
---
0 to 1
---
0 to 65535
0 to 999999.999
0 to 999999.999
0 to 65535
0 to 2
0 to 1
---
L90 Line Differential Relay
APPENDIX B
UNITS
STEP
FORMAT
s
0.1
F001
---
1
F300
---
1
F083
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F083
---
1
F300
---
1
F084
---
1
F109
---
1
F102
---
1
F001
ms
1
F011
ms
1
F011
---
1
F102
---
1
F519
0 (Reset Dominant)
---
1
F300
---
1
F300
---
1
F109
---
1
F102
---
---
F001
---
1
F102
---
---
F203
---
1
F300
s
0.001
F003
s
0.001
F003
---
1
F300
---
1
F109
---
1
F102
---
---
F001
DEFAULT
50
0
0 (Time-out)
0
0
0
0
0 (Time-out)
0
0 (Restore)
0 (Self-reset)
0 (Disabled)
0
0
0
0 (Disabled)
0
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
"Dig Element 1 "
0
0
0
0
0 (Self-reset)
0 (Disabled)
0
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents