B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 15 of 41)
ADDR
REGISTER NAME
4619
Channel Asymmetry Compensation
461A
Block GPS Time Reference
461B
Maximum Channel Asymmetry
461C
Round Trip Time
Breaker Control Global Settings (Read/Write Setting)
B
46F0
IEC 61850 XCBR 1 SelTimOut
Breaker Control (Read/Write Setting) (2 modules)
4700
Breaker 1 Function
4701
Breaker 1 Name
4704
Breaker 1 Mode
4705
Breaker 1 Open
4706
Breaker 1 Close
4707
Breaker 1 Phase A 3 Pole
4708
Breaker 1 Phase B
4709
Breaker 1 Phase C
470A
Breaker 1 External Alarm
470B
Breaker 1 Alarm Delay
470D
Breaker 1 Push Button Control
470E
Breaker 1 Manual Close Recall Time
4710
Breaker 1 IEC 61850 XCBR 1 SBOClass
4711
Breaker 1 IEC 61850 XCBR 1 SBOEna
4712
Breaker 1 Out Of Service
4713
Reserved (5 items)
4718
...Repeated for module number 2
Synchrocheck (Read/Write Setting) (2 modules)
4780
Synchrocheck 1 Function
4781
Synchrocheck 1 V1 Source
4782
Synchrocheck 1 V2 Source
4783
Synchrocheck 1 Maximum Voltage Difference
4785
Synchrocheck 1 Maximum Angle Difference
4786
Synchrocheck 1 Maximum Frequency Difference
4787
Synchrocheck 1 Dead Source Select
4788
Synchrocheck 1 Dead V1 Maximum Voltage
4789
Synchrocheck 1 Dead V2 Maximum Voltage
478A
Synchrocheck 1 Live V1 Minimum Voltage
478B
Synchrocheck 1 Live V2 Minimum Voltage
478C
Synchrocheck 1 Target
478D
Synchrocheck 1 Events
478E
Synchrocheck 1 Block
478F
Synchrocheck 1 Frequency Hysteresis
4790
...Repeated for module number 2
Demand (Read/Write Setting)
47D0
Demand Current Method
47D1
Demand Power Method
47D2
Demand Interval
47D3
Demand Input
Demand (Read/Write Command)
47D4
Demand Clear Record
Flexcurves A and B (Read/Write Settings)
4800
FlexCurve A (120 items)
48F0
FlexCurve B (120 items)
Modbus User Map (Read/Write Setting)
4A00
Modbus Address Settings for User Map (256 items)
B-22
RANGE
0 to 65535
0 to 65535
0 to 10
0 to 10
1 to 60
0 to 1
---
0 to 1
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 1000000
0 to 1
0 to 1000000
1 to 2
0 to 1
0 to 65535
0 to 65535
0 to 1
0 to 5
0 to 5
0 to 100000
0 to 100
0 to 2
0 to 5
0 to 1.25
0 to 1.25
0 to 1.25
0 to 1.25
0 to 2
0 to 1
0 to 65535
0 to 0.1
0 to 2
0 to 2
0 to 5
0 to 65535
0 to 1
0 to 65535
0 to 65535
0 to 65535
L90 Line Differential Relay
APPENDIX B
UNITS
STEP
FORMAT
---
1
F300
---
1
F300
ms
0.1
F001
ms
0.1
F001
s
1
F001
---
1
F102
---
---
F206
---
1
F157
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
s
0.001
F003
---
1
F102
s
0.001
F003
---
1
F001
---
1
F102
---
1
F300
s
1
F001
---
1
F102
---
1
F167
---
1
F167
V
1
F060
degrees
1
F001
Hz
0.01
F001
---
1
F176
pu
0.01
F001
pu
0.01
F001
pu
0.01
F001
pu
0.01
F001
---
1
F109
---
1
F102
---
1
F300
Hz
0.01
F001
---
1
F139
0 (Thrm. Exponential)
---
1
F139
0 (Thrm. Exponential)
---
1
F132
---
1
F300
---
1
F126
ms
1
F011
ms
1
F011
---
1
F001
DEFAULT
0
0
15
15
30
0 (Disabled)
"Bkr 1"
0 (3-Pole)
0
0
0
0
0
0
0
0 (Disabled)
0
1
0 (Disabled)
0
0
0 (Disabled)
0 (SRC 1)
1 (SRC 2)
10000
30
100
1 (LV1 and DV2)
30
30
70
70
0 (Self-reset)
0 (Disabled)
0
6
2 (15 MIN)
0
0 (No)
0
0
0