Calculation Example 1; Calculation Example 2 - GE L90 Instruction Manual

Line differential relay ur series
Hide thumbs Also See for L90:
Table of Contents

Advertisement

9.1 CT REQUIREMENTS
To check performance of a class C400 ANSI/IEEE CT, ratios 2000/1800/1600/1500 : 5 A connected at 1500:5, and where:
maximum I
= 14 000 A
fp
maximum I
= 12 000 A
fg
impedance angle of source and line = 78°
CT secondary leads are 75 m of AWG No. 10.
BURDEN CHECK:
ANSI/IEEE class C400 requires that the CT can deliver 1 to 20 times the rated secondary current to a standard B-4 burden
(4 Ω or lower) without exceeding a maximum ratio error of 10%.
The maximum allowed burden at the 1500/5 tap is
0.75 Ω
R
=
CT
0.2 VA
R
----------------- -
=
r
(
)
2
5 A
×
R
2
75 m
=
L
Therefore, the
Total Burden
which is OK.
KNEEPOINT VOLTAGE CHECK:
The maximum voltage available from the
The system X/R ratio
=
The CT Voltage for maximum phase fault is:
14000 A
---------------------------------- -
V
=
ratio of 300:1
The CT Voltage for maximum ground fault is:
12000 A
---------------------------------- -
V
=
ratio of 300:1
The CT will provide acceptable performance in this application.
To check the performance of an IEC CT of class 5P20, 15 VA, ratio 1500:5 A, assume identical parameters as for Example
Number 1.
BURDEN CHECK:
The IEC rating requires the CT deliver up to 20 times the rated secondary current without exceeding a maximum ratio error
of 5%, to a burden of:
15 VA
Burden
----------------
=
(
)
2
5 A
The total Burden = R
9
r
KNEEPOINT VOLTAGE CHECK:
Use the procedure shown for Example Number 1 above.
9-2
(
0.008 Ω
=
3.75 Ω
×
×
0.26 Ω
0.528 Ω
------------------- -
2
=
=
1000 m
0.75 Ω
R
R
R
=
+
+
=
CT
r
L
(
CT
1500 2000
=
tan
78°
4.71
.
=
×
(
)
×
(
4.71
1
0.75
0.26
+
+
+
×
(
)
×
(
4.71
1
0.75
0.52
+
+
+
0.6 Ω at the 5 A rated current
=
= 0.008 + 0.52 = 0.528 Ω, which is less than the allowed 0.6 Ω, which is OK.
+ R
l
L90 Line Differential Relay
) 4
×
3 Ω
1500 2000
. Now,
=
0.008 Ω
0.52 Ω
1.28 Ω
+
+
=
) 400
×
300 V
.
=
0.008 Ω
)
271.26 V (< 300 V, which is OK)
=
0.008 Ω
)
291.89 V (< 300 V, which is OK)
=
9 APPLICATION OF SETTINGS

9.1.2 CALCULATION EXAMPLE 1

. This is less than the allowed 3 Ω,

9.1.3 CALCULATION EXAMPLE 2

GE Multilin

Advertisement

Table of Contents
loading

Table of Contents