User-Programmable Self-Tests; Control Pushbuttons - GE L90 Instruction Manual

Line differential relay ur series
Hide thumbs Also See for L90:
Table of Contents

Advertisement

5.2 PRODUCT SETUP
!
PATH: SETTINGS
PRODUCT SETUP
# USER-PROGRAMMABLE
# SELF TESTS
All major self-test alarms are reported automatically with their corresponding FlexLogic™ operands, events, and targets.
Most of the Minor Alarms can be disabled if desired.
When in the "Disabled" mode, minor alarms will not assert a FlexLogic™ operand, write to the event recorder, display target
5
messages. Moreover, they will not trigger the
minor alarms continue to function along with other major and minor alarms. Refer to the Relay Self-Tests section in Chapter
7 for additional information on major and minor self-test alarms.
!
PATH: SETTINGS
PRODUCT SETUP
# CONTROL
# PUSHBUTTON 1
The three standard pushbuttons located on the top left panel of the faceplate are user-programmable and can be used for
various applications such as performing an LED test, switching setting groups, and invoking and scrolling though user-pro-
grammable displays, etc. Firmware revisions 3.2x and older use these three pushbuttons for manual breaker control. This
functionality has been retained – if the Breaker Control feature is configured to use the three pushbuttons, they cannot be
used as user-programmable control pushbuttons. The location of the control pushbuttons in the following figure.
An additonal four control pushbuttons are included when the L90 is ordered with twelve user programmable pushbuttons.
5-28
!"
USER-PROGRAMMABLE SELF TESTS
REMOTE DEVICE OFF
FUNCTION: Enabled
REMOTE DEVICE OFF
MESSAGE
FUNCTION: Enabled
PRI. ETHERNET FAIL
MESSAGE
FUNCTION: Disabled
SEC. ETHERNET FAIL
MESSAGE
FUNCTION: Disabled
BATTERY FAIL
MESSAGE
FUNCTION: Enabled
SNTP FAIL
MESSAGE
FUNCTION: Enabled
IRIG-B FAIL
MESSAGE
FUNCTION: Enabled
ANY MINOR ALARM
!"

CONTROL PUSHBUTTONS

CONTROL PUSHBUTTON 1
FUNCTION: Disabled
CONTROL PUSHBUTTON 1
MESSAGE
EVENTS: Disabled
L90 Line Differential Relay

5.2.12 USER-PROGRAMMABLE SELF-TESTS

Range: Disabled, Enabled.
Valid for units equipped with CPU Type C or D.
Range: Disabled, Enabled.
Valid for units equipped with CPU Type C or D.
Range: Disabled, Enabled.
Valid for units equipped with CPU Type C or D.
Range: Disabled, Enabled.
Valid for units equipped with CPU Type D.
Range: Disabled, Enabled.
Range: Disabled, Enabled.
Valid for units equipped with CPU Type C or D.
Range: Disabled, Enabled.
or
messages. When in the "Enabled" mode,
ANY SELF-TEST
5.2.13 CONTROL PUSHBUTTONS
!
CONTROL PUSHBUTTON 1(7)
Range: Disabled, Enabled
Range: Disabled, Enabled
5 SETTINGS