Autoreclose - GE L90 Instruction Manual

Line differential relay ur series
Hide thumbs Also See for L90:
Table of Contents

Advertisement

5.6 CONTROL ELEMENTS
!"
PATH: SETTINGS
CONTROL ELEMENTS

# AUTORECLOSE

#
5
5-182
!"
AUTORECLOSE
AR FUNCTION:
Disabled
AR MODE:
MESSAGE
1 & 3 Pole
AR MAX NUMBER OF
MESSAGE
SHOTS: 2
AR BLOCK BKR1:
MESSAGE
Off
AR CLOSE TIME BKR 1:
MESSAGE
0.10 s
AR BKR MAN CLOSE:
MESSAGE
Off
AR BLK TIME UPON MAN
MESSAGE
CLS:
10.00 s
AR 1P INIT:
MESSAGE
Off
AR 3P INIT:
MESSAGE
Off
AR 3P TD INIT:
MESSAGE
Off
AR MULTI-P FAULT:
MESSAGE
Off
BKR ONE POLE OPEN:
MESSAGE
Off
BKR 3 POLE OPEN:
MESSAGE
Off
AR 3-P DEAD TIME 1:
MESSAGE
0.50 s
AR 3-P DEAD TIME 2:
MESSAGE
1.20 s
AR 3-P DEAD TIME 3:
MESSAGE
2.00 s
AR 3-P DEAD TIME 4:
MESSAGE
4.00 s
AR EXTEND DEAD T 1:
MESSAGE
Off
AR DEAD TIME 1
MESSAGE
EXTENSION: 0.50 s
AR RESET:
MESSAGE
Off
AR RESET TIME:
MESSAGE
60.00 s
L90 Line Differential Relay
!
AUTORECLOSE
Range: Disabled, Enabled
Range: 1 & 3 Pole, 1 Pole, 3 Pole-A, 3 Pole-B
Range: 1, 2
Range: FlexLogic™ operand
Range: 0.00 to 655.35 s in steps of 0.01
Range: FlexLogic™ operand
Range: 0.00 to 655.35 s in steps of 0.01
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: 0.00 to 655.35 s in steps of 0.01
Range: 0.00 to 655.35 s in steps of 0.01
Range: 0.00 to 655.35 s in steps of 0.01
Range: 0.00 to 655.35 s in steps of 0.01
Range: FlexLogic™ operand
Range: 0.00 to 655.35 s in steps of 0.01
Range: FlexLogic™ operand
Range: 0 to 655.35 s in steps of 0.01
5 SETTINGS