Connecting Enervista Ur Setup With The L90 - GE L90 Instruction Manual

Line differential relay ur series
Hide thumbs Also See for L90:
Table of Contents

Advertisement

1 GETTING STARTED
10. Click Finish to end the installation. The L90 device will be added to the list of installed IEDs in the enerVista Launch-
pad window, as shown below.
This section is intended as a quick start guide to using the enerVista UR Setup software. Please refer to the enerVista UR
Setup Help File and Chapter 4 of this manual for more information.
a) CONFIGURING AN ETHERNET CONNECTION
Before starting, verify that the Ethernet network cable is properly connected to the Ethernet port on the back of the relay. To
setup the relay for Ethernet communications, it will be necessary to define a Site, then add the relay as a Device at that site.
1.
Install and start the latest version of the enerVista UR Setup software (available from the GE enerVista CD or online
from
http://www.GEindustrial.com/multilin
2.
Select the "UR" device from the enerVista Launchpad to start enerVista UR Setup.
3.
Click the Device Setup button to open the Device Setup window, them click the Add Site button to define a new site.
4.
Enter the desired site name in the "Site Name" field. If desired, a short description of site can also be entered along
with the display order of devices defined for the site. Click the OK button when complete.
5.
The new site will appear in the upper-left list in the enerVista UR Setup window. Click on the new site name and then
click the Device Setup button to re-open the Device Setup window.
6.
Click the Add Device button to define the new device.
7.
Enter the desired name in the "Device Name" field and a description (optional) of the site.
8.
Select "Ethernet" from the Interface drop-down list. This will display a number of interface parameters that must be
entered for proper Ethernet functionality.
Enter the relay IP address (from
in the "IP Address" field.
Enter the relay Modbus address (from the
BUS SLAVE ADDRESS
Enter the Modbus port address (from the
MODBUS TCP PORT NUMBER
9.
Click the Read Order Code button to connect to the L90 device and upload the order code. If an communications error
occurs, ensure that the three enerVista UR Setup values entered in the previous step correspond to the relay setting
values.
GE Multilin
(see previous section for installation instructions).
!
SETTINGS
PRODUCT SETUP
PRODUCT SETUP
setting) in the "Slave Address" field.
PRODUCT SETUP
setting) in the "Modbus Port" field.
L90 Line Differential Relay
1.3 ENERVISTA UR SETUP SOFTWARE

1.3.3 CONNECTING ENERVISTA UR SETUP WITH THE L90

!"
COMMUNICATIONS
!"
COMMUNICATIONS
!"
COMMUNICATIONS
!"
!
NETWORK
IP ADDRESS
!"
!
MODBUS PROTOCOL
MOD-
!"
!"
MODBUS PROTOCOL
1-7
1
)