Step
Action
3
Connect the module's wire harness to the control (11, 12, 13 and 14). Plug the connector on the harness to
the module.
When mounting remotely, homerun each module to the control. The table below shows the maximum wire
run lengths. Refer to the instructions provided with the 4204CF for its maximum permissible wire lengths.
Wire Gauge
#22
#20
#18
#16
DIP SWITCH
(WHITE AREAS DENOTE SWITCH HANDLES)
ENABLES/DISABLES COVER TAMPER. ON = TAMPER DISABLED,
OFF = TAMPER ENABLED. SHOWN DISABLED AS SHIPPED.
DETERMINE 4204CF'S ADDRESS: CONTROL'S INSTRUCTIONS
"0" ADDRESS SETTING SHOWN (AS SHIPPED).
4204CF
DIP SWITCH
FOR SETTING DEVICE
ADDRESS AND
ENABLING/DISABLING TAMPER
COVER TAMPER (REED) SWITCH
4-PIN CONSOLE
PLUG
EITHER OR BOTH
CAN BE USED
TB1
13
14
15
16
YEL
DATA IN FROM CONTROL
BLK
GROUND
GRN
DATA OUT TO CONTROL
RED
12VDC; SUPPLIES POWER TO MODULE CIRCUITRY (INCLUDING APPLIANCE OUTPUT
RELAY COILS). CURRENT DRAIN AT 12V IS: 25mA + (80mA PER ACTIVE OUTPUT).
Maximum Length
125 feet
200 feet
300 feet
500 feet
SWITCH
OFF
ON
NUMBER
0
1
2
3
4
5
2
ON — ON — ON — ON — ON — ON — ON — ON —
3
ON ON — — ON ON — — ON ON — — ON ON — —
4
ON ON ON ON — — — — ON ON ON ON — — — —
5
ON ON ON ON ON ON ON ON — — — — — — — —
6
ON ON ON ON ON ON ON ON
DIP SWITCH (WHITE AREAS DENOTE SWITCH HANDLES)
POSITION 7: NO FUNCTION
POSITIONS 2-6:
DETERMINE 4204'S ADDRESS: CONTROL'S INSTRUCTIONS SPECIFY ADDRESS
TO USE. "0" ADDRESS SETTING SHOWN (AS SHIPPED).
POSITION 1: ENABLES/DISABLES COVER TAMPER. ON = TAMPER DISABLED,
OFF = TAMPER ENABLED. SHOWN DISABLED AS SHIPPED.
4204
DIP SWITCH
FOR SETTING DEVICE ADDRESS
AND ENABLING/DISABLING TAMPER
COVER TAMPER (REED) SWITCH
4-PIN TOUCHPAD PLUG
EITHER OR BOTH
CAN BE USED
TB1
13
14
15
Must be connected to a
power-limited source.
Supervised

Figure 3-21: 4204 Relay Module

OFF
ON
POSITION 1
POSITIONS 2-6
SPECIFY ADDRESS TO USE.
POSITION 7
FOR UL COMMERCIAL FIRE INSTALLATIONS, ONLY ONE NOTIFICATION APPLIANCE MODULE MAY BE USED, AND ONLY ONE
NO FUNCTION
NOTIFICATION APPLIANCE OUTPUT (A or B) MAY BE USED ON THAT MODULE.
TB2
12
NOTIFICATION
APPLIANCE
11
NC
OUTPUT B
10
NC
2K EOLR
EOL20
9
POLARIZED
8
NC
NOTIFICATION
7
NC
APPLIANCES
6
NOTIFICATION
APPLIANCE
5
OUTPUT A
4
2K EOLR
EOL20
3
2
NC
POWER FOR NOTIFICATION APPLIANCE OUTPUTS
1
NC
A & B 8-30 VDC REGULATED OR VFW. UP TO 2.4A
DEPENDING ON NOTIFICATION APPLIANCE CURRENT.

Figure 3-22: 4204CF Relay Module

DIP SWITCH SETTINGS

4204 ADDRESS SETTINGS
("—" means "OFF")
8
9 10 11 12 13 14 15
16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
6
7
ON — ON — ON — ON — ON — ON — ON — ON —
ON ON — — ON ON — — ON ON — — ON ON — —
ON ON ON ON — — — — ON ON ON ON — — — —
ON ON ON ON ON ON ON ON — — — — — — — —
ON ON ON ON ON ON ON ON
— — — — — — — —
RELAY
4
TYPICAL
(SHOWN "OFF")
RELAY
3
RELAY
2
RELAY
1
16
YEL
DATA IN FROM CONTROL
BLK
(–) GROUND
GRN
4204 CONNECTIONS
DATA OUT TO CONTROL
RED
(+) 12VDC
SWITCH
NUMBER
0
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15
2
ON — ON — ON — ON — ON — ON — ON — ON —
3
ON ON — — ON ON — — ON ON — — ON ON — —
4
ON ON ON ON — — — — ON ON ON ON — — — —
5
ON ON ON ON ON ON ON ON — — — — — — — —
ON ON ON ON ON ON ON ON
ON ON ON ON ON ON ON ON
6
SPECIAL APPLICATIONS CIRCUITS
ALARM POLARITY SHOWN
EACH OUTPUT PROVIDES
STYLE Y SUPERVISION
EACH OUTPUT RATED 1.2A MAX.
MAX LINE IMPEDANCE IS 1 OHM.
USE NOTIFICATION APPLIANCES
COMPATIBLE WITH POWER SUPPLY
VOLTAGE RATING
43
— — — — — — — —
4204-01-V1
C
NC
NO
C
If switching power
NC
through a relay, the
NO
power must be from a
power-limited source.
C
Relays are programmable
NC
but outputs are not
supervised.
NO
C
NC
NO
TB2
4204-02-V2
4204CF ADDRESS SETTINGS
("—" means "OFF")
16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
ON — ON — ON — ON — ON — ON — ON — ON —
ON ON — — ON ON — — ON ON — — ON ON — —
ON ON ON ON — — — — ON ON ON ON — — — —
ON ON ON ON ON ON ON ON — — — — — — — —
— — — — — — — —
— — — — — — — —
NOTIFICATION APPLIANCE AND CONSOLE DATA
OUTPUTS ARE POWER-LIMITED.
ALL POWER-LIMITED WIRING MUST BE SEPARATED
FROM NON-POWER-LIMITED AND HIGH-VOLTAGE
WIRING BY 1/4" (6.4mm).
ALL CIRCUITS ARE SUPERVISED AND POWER-LIMITED
WHEN POWERED BY THE CONTROL PANEL.
NFPA-72 COMPLIANT.
4204CF-004-V3