Wiring 2-Wire Smoke Detectors to Zones 1 and 2
2K EOL resistors must be used on fire zones and must be connected across the loop wires of each zone at the
last detector.
To wire 2-wire smoke detectors to zone 1 and/or zone 2, perform the following steps:
Step
Action
1
Select 2-wire smoke detectors from the list of compatible detectors.
2
Connect 2-wire smoke detectors across zone 1 (terminals 15 and 16), and/or zone 2 (terminals 17 and 18) as
shown in Figure 3-12. Observe proper polarity when connecting the detectors.
3
Connect the EOL resistor at the last detector in the loop across the zone 1 terminals. The EOL resistor
must be connected across the loop wires at the last detector.

Figure 3-12: 2-Wire Smoke Detector on Zone 1 (for zone 2 use terminals 17 and 18)

Using 4-Wire Smoke Detectors on Zones 1-8
For ULC fire installations, 4-Wire Smoke Detectors must not be connected to the fire transmitter. These devices
U LC
must be connected to the Fire Alarm Control Panel.
You may use as many 4-wire smoke detectors as can be powered from the panel's Auxiliary Power output without
exceeding the output's rating (1A (for Canada 650mA)).
Auxiliary power to 4-wire smoke detectors is not automatically reset after an alarm, and therefore must be
momentarily interrupted using the auxiliary relay.
Compatible 4-Wire Smoke Detectors
Use any UL Listed 4-wire smoke detector that is rated for 12VDC operation and that has alarm reset time not exceeding
6 seconds. Some compatible 4-wire smoke detectors are listed below.
DETECTOR TYPE
4-Wire Photoelectric Smoke Detector
4-Wire Photoelectric Smoke Detector w/Heat Detector
4-Wire Photoelectric Smoke Detector w/Sounder & Heat Detector
4-Wire Photoelectric Smoke Detector w/Aux. Relay & Heat Detector
4-Wire Photoelectric Smoke w/Aux. Relay, Sounder & Heat Detector
End of Line Power Supervision Relay for FSA-410 Series Smoke Detectors
Polarity reversal module for FSA-410 series Smoke Detectors
4-Wire Photoelectric Smoke Detector
4-Wire Photoelectric Smoke Detector w/Heat Detector
4-Wire Photoelectric Smoke Detector w/Sounder & Heat Detector
4-Wire Photoelectric Smoke Detector w/Aux. Relay & Heat Detector
4-Wire Photoelectric Smoke Detector w/Aux. Relay, Sounder & Heat Detector
4-Wire Photoelectric Smoke Detector w/Aux. Relay, Sounder & Isolated Heat Detector
4-Wire Photoelectric Air Duct Smoke Detector, Extended Air Speed Range
4-Wire Ionization Air Duct Smoke Detector
2-WIRE SMOKE
DETECTOR
34
15
16
MANUFACTURER
MODEL #
DSC
FSA-410B
DSC
FSA-410BT
DSC
FSA-410BST
DSC
FSA-410BRT
DSC
FSA-410BRST
DSC
RM-2
DSC
PRM-4WC
System Sensor
4W-B
System Sensor
4WT-B
System Sensor
4WTA-B
System Sensor
4WTR-B
System Sensor
4WTAR-B
System Sensor
4WITAR-B
System Sensor
DH100ACDCLP
System Sensor
DH100ACDCI