Honeywell VISTA-32FBPT Installation And Setup Manual page 28

Commercial fire and burglary partitioned security system with scheduling
Hide thumbs Also See for VISTA-32FBPT:
Table of Contents

Advertisement

U L
Burglary Notification Appliance Circuits must be programmed for a timeout of 16 minutes or longer.
Commercial fire alarm systems require Notification Appliance Circuits to be supervised.
Notification Appliance Circuit Supervision
The VISTA-32FBPT monitors the Notification Appliance Circuits wiring for open and short circuit faults while the
output is inactive. The system provides a trouble indication (Zone 970 Bell 1; 971 Bell 2) when an open occurs. When a
short occurs between the Bell (+) and Bell (-) terminal wiring, or between the Bell (+) terminal wiring and earth ground
the system provides a trouble indication (972 Earth Ground).
The VISTA-32FBPT indicates the trouble condition regardless of whether the system is armed or disarmed. The zone
displays on the keypads, reports to the event log, and transmits to the central station (if programmed) on Partition 1.
The trouble is cleared from the display by entering the user code + OFF.
Use only UL Listed sounding devices for UL installations.
U L
In Commercial Fire installations, the 4204CF cannot be used to drive sounders in the same audible area as
sounders connected to the alarm outputs of the control panel.
For ULC fire installations, alarm indicating devices must not be connected to the fire transmitter. These
U LC
devices must be connected to the Fire Alarm Control Panel.
Synchronization Requirements for Commercial Fire
Notification Appliance Circuit outputs must be wired to a Sync Module if more than one device is used. Follow
instructions provided with Sync Module. Be sure to use the compatible Sync Module for the Alarm Indicating Device
selected.
MANUFACTURER
GENTEX
SYSTEM SENSOR
WHEELOCK
All visual notification appliances within the same physical area must be synchronized.
U L
The bell outputs are listed as Special Application Notification Appliance Circuits.
Compatible Alarm Indicating Devices
ALARM INDICATING DEVICE TYPE
UL listed Grade A Bell in Housing
RX7 UL Indoor Sounder, 12V
Horn Strobe 2w
Horn Strobe 2w
Horn Strobe 4w
Horn Strobe 4w
Chime, 12/24V, Selectable Tone & Volume, Red
Chime, 12/24V, Selectable Tone & Volume, White
Chime/Strobe, 12/24V, Selectable Candela, Tone & Volume, Red
Chime/Strobe, 12/24V, Selectable Candela, Tone & Volume, White
Horn, 12/24V, Red
Horn, 12/24V, White
Horn, 12/24V, Outdoor, Red
2-Wire Wall Mount Horn/Strobe, 12/24V, Standard Candela, Red
2-Wire Wall Mount Horn/Strobe, 12/24V, High Candela, Red
2-Wire Wall Mount Horn/Strobe, 12/24V, Standard Candela, Red, Outdoor
2-Wire Wall Mount Horn/Strobe, 12/24V, High Candela, Red, Outdoor
2-Wire Wall Mount Horn/Strobe, 12/24V, Standard Candela, White
2-Wire Wall Mount Horn/Strobe, 12/24V, High Candela, White
SYNC MODULE MODEL NUMBER
AVSM
MDL
DSM
MANUFACTURER
Honeywell/ADEMCO
ADT
GENTEX
GENTEX
GENTEX
GENTEX
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
28
MODEL #
AB12M
875936B
GEC3-12, GES3-12, GEH-12
GEC3-12, GES3-12, GEH-12
GEC3-12, GES3-12, GEH-12
GEC3-12, GES3-12, GEH-12
CHR
CHW
CHSR
CHSW
HR
HW
HRK
P2R
P2RH
P2RK
P2RHK
P2W
P2WH