Output Relay Module

PROMPT
01 SUPERVISED CF?
0

Communicator

If you selected device type 6, the 6160 and 6160CR-2 Keypad functions similarly to the 7720P Programming Tool. See Figure
1 for the functions of the keys on the 6160CR-2.
Figure 1: 6160CR-2 Key Functions for Programming the Communicator
Each key has two possible functions: a normal function and a SHIFT function. To perform a normal key function, simply press
the desired key. To perform a SHIFT key function, press SHIFT key, then press desired function key.

Normal and SHIFT key Functions:

Key
BS/ESC
[BS]: Press to delete entry
Also, can reset EEPROM defaults *
↓/↑
[↓]: Scroll down programming
N/Y
[N]: Press for "NO" answer
SHIF
Press before pressing a SHIFT key function. Will light READY LED. LED goes out once a key is
T
pressed. Press again for each SHIFT function desired.
1/A
[1]: For entering the number 1
2/B
[2]: For entering the number 2
3/C
[3]: For entering the number 3
4/D
[4]: For entering the number 4
5/E
[5]: For entering the number 5
6/F
[6]: For entering the number 6
7/S
[7]: For entering the number 7
8/T
[8]: For entering the number 8
9/X
[9]: For entering the number 9
*/SPACE
[*]: Not used with 7845i-ent
0
[0]: For entering the number 0
#/ENTER
[#/ENTER]: Press to accept entries
* Active only when the "REVIEW?" prompt is displayed.
EXPLANATION
If you selected device type 04 (relay module), this prompt appears. Enter 1 if the unit is a 4204CF. If not,
enter 0. If you enter 1, only Relay 1 (Output A) and Relay 3 (Output B) on each module may be programmed
for functions.
NOTE: For Commercial Fire installations, only one notification appliance module may be used, and only one
notification appliance output (A or B) may be used on that module.
Press [✱] to accept entry.
6160
Normal Key Function
ARMED
READY
POWER
ALARM
SILENCED
SUPV
TROUBLE
NOTE: The 6160CR-2 must be used in Commercial
SHIFT Key Function
[ESC]: Press to quit Program Mode
[↑]: Scroll up programming
[Y]: Press SHIFT-Y for "YES" answer
[A]: Used for entering C.S. ID number
[B]: Used for entering C.S. ID number
[C]: Used for entering C.S. ID number
[D]: Used for entering C.S. ID number
[E]: Used for entering C.S. ID number
[F]: Used for C.S. ID & FAST Mode
[S]: Press to display diagnostic status
[T]: Press to send TEST messages
[X]: Press to reset the 7845i-ent
[SPACE]: Not used with 7845i-ent
No SHIFT function
No SHIFT function
– 32 –
1
2
3
OFF
AWAY
STAY
4
5
6
MAX
TEST
BYPASS
7
8
9
CODE
CHIME
INSTANT
0
READY
#
6160CR-2
Fire installations