Mounting The Control In The Attack-Proof Cabinet (Suitable For Commercial Fire/Commercial Burglary Applications); Figure 3-4: Cabinet Attack Resistance Considerations - Honeywell VISTA-32FBPT Installation And Setup Manual

Commercial fire and burglary partitioned security system with scheduling
Hide thumbs Also See for VISTA-32FBPT:
Table of Contents

Advertisement

Mounting the Control in the Attack-Proof Cabinet (Suitable for Commercial
Fire/Commercial Burglary Applications)
If you are installing a Vista-32FBPT in the attack-proof cabinet with the external transformer, follow the steps below.
Step
Action
1
Before mounting the circuit board, remove the metal knockouts for the wiring entry that you will be using.
DO NOT ATTEMPT TO REMOVE THE KNOCKOUTS AFTER THE CIRCUIT BOARD HAS BEEN
INSTALLED.
2
Using fasteners or anchors (not supplied), mount the control cabinet to a sturdy wall in a clean, dry area
that is not readily accessible to the general public. The back of the cabinet has four holes for this purpose.
Installing the Cabinet Lock
To install the lock, perform the following steps:
Step
Action
1
Remove the cabinet door, and the lock knockout from the door. Insert the key into the lock (see Figure 3-1).
2
Position the lock in the hole, making certain that the latch will make contact with the latch bracket when
the door is closed.
3
When correctly positioned, push the lock until its snap tabs hold it securely.
Use a Honeywell No. K4445 Lock (supplied).
To provide certificated burglary service for UL installations, refer to the special requirements and Figure 3- 4
Cabinet Attack Resistance Considerations to follow. NOTE: A COM-UL attack-proof cabinet must be used
U L
with the Vista-32FBPT for Commercial Fire/Commercial Burglary applications. No other attack-proof
cabinet may be used.
Mercantile Premises Listing Guidelines
The panel door must be supervised. Mount the clip-on tamper switch (supplied) to the cabinet's right side wall, and
wire it to zone 6.
Assign zone 6 to a burglary partition. Program it for day trouble/night alarm (zone type 5) when only one burglary
partition is used. Program it for 24-hr. audible alarm (zone type 7) when more than one burglary partition is used.
Enable field 3*17 so that the system responds to a ground fault in accordance with its zone type rather than a
ground fault response.
All wiring between the transformer and panel must be run in conduit. Remaining wires do not need to be run in
conduit.
All unused knockouts must be plugged using the disc plugs and carriage bolts (supplied), as indicated in Figure 3-2.
Fasten the cabinet door to the cabinet backbox using the 15 one-inch-long Phillips-head screws (supplied) after all
wiring, programming, and checkout procedures have been completed.
RUN BELL WIRES
IN CONDUIT
PLATE
PLUG THESE
KNOCKOUTS
PLUG THIS
KNOCKOUT
Mercantile Safe and Vault Listing Guidelines
Follow the guidelines given above for Mercantile Premises listing.
PC
BOARD
MOUNTING
PLUG THESE
SCREWS
KNOCKOUTS
(3)

Figure 3-4: Cabinet Attack Resistance Considerations

PLUG THIS
KNOCKOUT
TO PLUG AN UNUSED KNOCKOUT OPENING,
REMOVE KNOCKOUT AND INSTALL A PAIR OF
DISC PLUGS AND A CARRIAGE BOLT AS SHOWN.
CABINET
KNOCKOUT
OPENING
HEX NUT AND
WASHER
RUN ALL REMAINING
WIRE THROUGH HERE
23
DISC PLUGS (DIMPLES IN DISC
PLUG SHOULD REGISTER INSIDE
KNOCKOUT OPENING)
CARRIAGE BOLT
CABINET SIDE WALL
(OUTSIDE)
fire_burg_cab-001-V0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents