Program feature or option
28 POWER-UP IN PREV.
STATE
37 DOWNLOAD COMMAND
ENABLES
41 NORMALLY CLOSED OR
EOLR (ZONES 3-8)
42 DIAL TONE PAUSE
44 RING DETECTION
COUNT
56 DYNAMIC SIGNAL
DELAY
77 AUTO TRBL RSTR
80 ZONE TYPE 9 -10, 14
RESTORE
1
12 PROGRAM
NOTIFICATION
1
13 SYS. SENSOR REV.
RELAY
1
18 AFFECTS LOBBY
(PARTITION – SPECIFIC)
1
19 ARMS LOBBY
(PARTITION – SPECIFIC)
1
22 thru 1
25 CROSS-
ZONING PAIRS (1 – 4)
1
28 RF TX LOW BATTERY
SOUND
1
29 RF TX LOW BATTERY
REPORTING
1
30 RF RCVR CHECK-IN
INTERVAL
1
31 RF TX CHECK-IN
INTERVAL
1
35 ACS DLR ENABLES
1
44 RF KEYPAD TAMPER
DETECTION
Permitted in
UL864? Y/N
0 = disable
Y
1 = enable
0 = disable
N
1 = enable
0 = EOLR supervision
N
1 = N.C. loops
Enter the wait time for dial tone
Y
detection:
0 = 5 seconds; 1 = 11 seconds; 2 = 30
seconds.
Enter 00 to disable ring detection.
N
Enter 01-14 for ring counts of 1-14.
Enter 15 to select Answering
Machine Defeat Mode
Enter 00-15 times 15 seconds.
Y
0 = disable
Y
1 = restore troubles only
2 = restore troubles and fire alarms
0 = disable
N
1 = enable
0 = no
Y
1 = yes
N
0=use neither Zone 1 or Zone 2
inputs
1=use Zone 1 input;
2=use Zone 2 input;
3=use Zone 1 and Zone 2 inputs.
0 = disable
N
1 = enable
0 = disable
N
1 = enable
Enter 001-032
N
Enter 000,000 to disable
0 = disarmed state only
N
1 = both armed and disarmed states
0 = disable
N
1 = enable
Enter 02–15 times 2 hours (4–30
N
hours)
Enter 00 to disable receiver
supervision
Enter 02–15 times 2 hours (4–30
N
hours)
Enter 00 to disable transmitter
supervision
N
0 = disable
1 = enable
N
0 = disable
1 = enable
Possible settings
8
Settings permitted in
UL 864
Must be set to "1" (enable).
Must be set to "0" for all
entries (disable).
Must be set to "0" (EOLR
Supervision).
Must be set to "0" (5 seconds).
Must be set to "00" (disable).
Must be set to "6" (90
seconds).
Must be set to "1" (restore
troubles only).
Must be set to "1" (enable) for
zone type 9.
Must be set to "1" (yes).
Not Used. Must be set to "0".
Must be set to "0" (disabled)
for partition 1.
Must be set to "0" (disabled)
for partition 1.
Must be set to "000,000"
(disabled) for fire zones.
Must be set to "1" (both
armed and disarmed states).
Must be set to "1" (enable).
Maximum is 02 (4 hours) for
fire installations.
Maximum is 02 (4 hours) for
fire installations.
Not used. Must be set to "0".
Not used. Must be set to "0".