PIR Anti-Mask:
panel when the lens has been blocked. For DIP switch settings related to this feature, refer to the motion
detector documentation. Anti-Mask can be enabled in zone programming if a zone type 04 (interior) or 10
(interior with delay) and input type 06 (serial poll) are selected. In the event masking occurs, the message "PIR
masked" will be displayed on the keypad, and a trouble report code is used to report the masking.
Smoke Detector Maintenance:
5193SD and 5193SDT V-Plex detectors, as well as the 5808W3.
Operation: When programmed as a "Smart Contact" in zone programming, a sensor which is capable of
providing a high or low sensitivity condition (e.g., sensor is dirty) will trigger a message on the keypad, a dialer
report, and an event log entry. The display message will indicate HSENSxxx or LSENSxxx, where xxx is the
zone number.
Fire Walk-Test Mode
Provides an automatic test of integrated V-Plex devices that have the automatic test feature.
Can display all fire zones that remain untested.
Can log test results in the event log.
Can report the test results to the central station.
Additional Features
Provides a Battery Protection feature that prevents the battery from going into deep discharge in case of a
prolonged AC power outage.
Provides two style-Y supervised Special Application Notification Appliance Circuits.
Supervision of Notification Appliance Circuits, phone lines, keypads, RF receivers, and output devices
Provides an auxiliary relay (form C) that can activate alarms troubles/supervisories, reset 4-wire smoke
detectors, or as a battery saver (removes power from non-critical loads 4 hours after AC power loss).
Provides up to 60 installer-defined, custom words that can be used for zone descriptors.
Provides 32 keypad macro commands (each macro is a series of keypad commands of up to 32 keystrokes) using
the A, B, C, and D keys by partition.
Provides cross-zone capability, which helps prevent false alarms by preventing a zone from going into alarm
unless its cross-zone is also faulted within a 5-minute period (does not apply to Fire zones).
Contains a built-in User Manual, which provides the end user with a brief explanation of the function of a key
when the user presses any of the function keys on the keypad for 5 seconds.
Provides trigger outputs, which may interface with Communication equipment or other devices such as a
keyswitch, a Honeywell access control system, or an automation system.
Provides an option to have trouble and supervisory conditions automatically clear from the display when the
zone returns to the ready/normal state (entry of Code + OFF is not required).
At least one 2-line alpha keypad (6160/6160CR-2) must be connected to the system for programming (if you are
using keypad programming), and must remain connected to the system in order to allow the primary user to program
additional user codes into the system at a later time.
Some motion detectors such as the DT7500SN have an "Anti-Mask" feature that will alert the
Provides Maintenance Signal support for certain smoke detectors, such as the