For true detector sensitivity tests, and for compliance with fire codes, you must enter 0 (NO) to this question.
PROMPT
LOG RESULTS?
0=NO
1=YES
C.S. TRANSMIT?
0=NO
1=YES
When the Test Mode is activated, the system will sound fire Notification Appliance Circuits (or any NAC having a non-
zero response type programmed in the #93 Menu Mode) for 3 seconds. The system will also send a Start of Walk-Test
message to the central station, and will light all keypad indicators (except the ARMED LED) and display window
segments to verify that they are working properly. The keypads will then display Fire Walk-Test in Progress and will
sound a single beep every 15 seconds while this test is active. Additionally, in this test mode RF receiver sensitivity is
reduced to 50% to ensure proper fire RF device mounting locations.
The system will build a list of all the fire zones (response types 9, 16, 17, 18) that need to be tested. These points will be
scrolled on the display. For each point, the keypad will display "UNTST XXX," where XXX is the point number, followed
by an alpha descriptor for the point.
If the auto-test option has been selected, the control panel will attempt to automatically test all of the polling loop points
that have a zone response type of 9 or 16. For points that must be manually tested, fault and reset each fire alarm
sensor in turn.
Each action should cause keypads to beep and fire Notification Appliance Circuits to ding. The keypads will display the
zone number and the associated alpha descriptor while the zone remains faulted. The system automatically issues a
smoke detector power reset about 10 seconds after it finds a fault on one of these zones, to allow faulted detectors to be
reset.
The system will automatically perform the smoke detector reset on zones 1 and 2, if programmed for fire, and on
the auxiliary relay and any other output device (relay) that is programmed for smoke detector reset.
To end the test, enter any security code and press OFF. An End of Walk-Test message will be sent to the central station
(if programmed). Note that the test will automatically end if no faults are detected within a 1-hour time period.

Burglary Walk-Test

This test causes the system to sound keypad beeps in response to faults on zones for the purpose of allowing proper zone
operation to be checked without triggering alarms. This test can be activated by any user by entering the corresponding
security code and pressing TEST while the burglary portion of the system is disarmed. UL requires that this test be
conducted on a weekly basis.
When this test is first entered, the system activates the alarm output for 3 seconds. The system sends a Start of Walk-
Test message to the central station. The keypad displays "Burg Walk Test in Progress" and sounds a single beep every
15 seconds while the test remains active.
Open and close each protected door and window in turn. Each action should produce three beeps from the keypad. Walk
in front of any motion detectors. Listen for three beeps when the detector senses movement. The keypad displays the
zone number and alpha descriptor while a door or window remains open or while a detector remains activated.
To end this test, enter any security code and press OFF. An End of Walk-Test message is sent to the central station.
The system automatically exits the Test mode if there is no activity (no doors or windows are opened and
closed, no motion detectors are activated, etc.) f or 60 minutes. The system beeps the keypad(s) twice every 5
seconds during the last 5 minutes as a warning that it is about to exit the Test mode and return to normal
operation.
EXPLANATION
Enter 1 (YES) to have the system log each point as it is tested. A list of untested points will also be logged.
Enter 0 (NO) if you do not want to log the results.
The next prompt will only be displayed if Contact ID report format has been selected.
Enter 1 (YES) to have the results of the test sent to the central station. This report will consist of a list of
points that have been tested followed by a list of points that have not been tested.
Enter 0 (NO) if you do not want to report the results. A Walk-Test Start and Walk-Test End report will be
sent in either case (if programmed).