Honeywell ADEMCO VISTA SERIES Programming Manual

Honeywell ADEMCO VISTA SERIES Programming Manual

Hide thumbs Also See for ADEMCO VISTA SERIES:
Table of Contents

Advertisement

ADEMCO VISTA SERIES
VISTA-20P / VISTA-20PSIA
VISTA-15P / VISTA-15PSIA
Security Systems
Programming Guide
K5305-1PRV8 5/11 Rev. A

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell ADEMCO VISTA SERIES

  • Page 1 ADEMCO VISTA SERIES VISTA-20P / VISTA-20PSIA VISTA-15P / VISTA-15PSIA Security Systems Programming Guide K5305-1PRV8 5/11 Rev. A...
  • Page 2: Recommendations For Proper Protection

    RECOMMENDATIONS FOR PROPER PROTECTION The Following Recommendations for the Location of Fire and Burglary Detection Devices Help Provide Proper Coverage for the Protected Premises. Recommendations For Smoke And Heat Detectors With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations contained in the National Fire Protection Association's (NFPA) Standard #72 noted below.
  • Page 3: Table Of Contents

    TABLE OF CONTENTS PROGRAMMING MODE COMMANDS........................4 DATA FIELD PROGRAMMING FORM ........................5 CONFIGURABLE ZONE TYPES WORKSHEET ....................18 ∗ ∗ ∗ ∗ 56 ZONE PROGRAMMING MENU MODE......................19 ∗ ∗ ∗ ∗ 58 EXPERT ZONE PROGRAM MODE........................21 WIRELESS KEY PROGRAMMING TEMPLATES ....................22 ∗ ∗ ∗ ∗ 57 FUNCTION KEY PROGRAMMING MENU MODE...................24 OUTPUT DEVICE PROGRAMMING GENERAL INFORMATION (*79/*80 Menu Mode)........25 ∗...
  • Page 4: Programming Mode Commands

    PROGRAMMING MODE COMMANDS Compatibility: This document applies to systems with microprocessor version 9.1 or higher. TO ENTER PROGRAMMING MODE (using an alpha keypad connected to the control): A. POWER UP, then press [ , ] and [#] at the same time, within 50 seconds of powering up (this method must be used if , 98 was used to exit program mode).
  • Page 5: Data Field Programming Form

    DATA FIELD PROGRAMMING FORM Entries apply to the ADEMCO VISTA-15P/VISTA-15PSIA and ADEMCO VISTA-20P/VISTA-20PSIA controls, except entries shown in dashed boxes, which apply only to the VISTA-20P/VISTA-20PSIA (partition entries) and are not applicable to the VISTA-15P/VISTA-15PSIA. In addition, where noted, certain fields have special settings when used with the SIA panels V20PSIA/V15PSIA (indicated by with heavy borders and reverse type throughout for easy identification).
  • Page 6 Access Code For Phone Module ∗ ∗ ∗ ∗ 28 [00] 00 = disable (Partition 1 only) 1st digit: enter 1–9 You must assign a 2-digit access code for the 4286 Phone Module, if 2nd digit: enter # + 11 for "∗", or # + 12 used.
  • Page 7 Confirmation Of Arming Ding ∗ ∗ ∗ ∗ 38 [0,0] 0 = no Part. 1 Part. 2 1 = yes (wired keypads and RF) Confirmation of arming is 1/2-sec external sounder “ding.” 2 = yes, RF only (except 5827, If 1 selected, ding occurs when closing report is sent if open/close 5827BD) reporting is enabled, or at the end of Exit Delay.
  • Page 8 Split/Dual Reporting ∗ ∗ ∗ ∗ 49 0 = Standard/backup reporting only (all Backup Reporting: All reports are sent only to the primary number to primary) unless unsuccessful after 8 attempts. If unsuccessful, the system will 1-5 = see table at right make up to 8 attempts to send all reports to the secondary number.
  • Page 9 ∗ ∗ ∗ ∗ 55 Dynamic Signaling Priority / For AAV Path Select: • If using the UVS system or AVS system with non-ECP connection, AAV Path Select (continued) option 0 must always be used. • If using the AVS system with ECP connection, either option (0 or 1) may be used, but note the following: IMPORTANT: If option “1”...
  • Page 10 Open Report Code ∗ ∗ ∗ ∗ 65 [0,0,0] System Reporting Note above *59. See above for entries. Part. 1 Part. 2 Common Sent upon disarming the system in the selected partitions. See UL Arm Away/Stay Rpt Code ∗ ∗ ∗ ∗ 66 [0,0,0,0,0,0] See above for entries.
  • Page 11 OUTPUT AND SYSTEM SETUP ( 77 – ∗ ∗ ∗ ∗ 77 Daylight Saving Time Start/End [3][11] Month Enter the start and end month for daylight saving time, if applicable to 0 = Disabled the region. 1-9 = Jan.-Sept. (1 = Jan, 2 = Feb, etc) #+10 = October #+11 = November #+12 = December...
  • Page 12 AAV “Listen in” session Entry 2: Remote Interactive Services cannot take place. (RIS) enable UL: for AAV, must use ADEMCO UVCM module or Honeywell AVS system; 0 = RIS disabled Exit Delay Restart/Reset must be disabled 1 = not applicable 2 = RIS enabled SIA Guidelines: Exit Delay should be enabled.
  • Page 13 Reports In Armed Period Per ∗ ∗ ∗ ∗ 93 [1,0] Zone (Swinger Suppression) Restrict V20PSIA/V15PSIA Restrict Report Pairs: Report Pairs Unlimited Reports Enable 0 = Unlimited Reports Selection limits the number of alarm/alarm restore message pairs per 1 = 1 report pair per zone per armed zone sent to the CS in an armed period.
  • Page 14 ∗ ∗ ∗ ∗ 160 Pager 1 Phone No. Enter up to 20 digits. 0–9 If entering fewer than 20 digits, exit by pressing [∗] + next field number. #+11 = ' , ' To clear entries, press ∗160∗. #+12 = '#' #+13 = 2-second pause ∗...
  • Page 15 Pager Delay Option For Alarms ∗ ∗ ∗ ∗ 172 0 = none This field determines the delay of alarm reports to the pager. This gives 1 = 1 minute the Central Station enough time to verify the alarm report it received 2 = 2 minutes before the dialer attempts to dial the pager.
  • Page 16 ∗ ∗ ∗ ∗ 182 Configurable Zone Type 90 (0-9, #+10=10, #+11=11, #+12=12, #+13=13, #+14=14, #+15=15). Enter the appropriate value for each entry, 1-10, based on the charts provided in the Configurable Zone Type Worksheet section. Each entry is the sum of the values of its selected options To calculate the value for each entry, add the values of the selected options in each of the entry’s columns shown in the respective chart (one option per column).
  • Page 17 Keypad 2 Device Address 17 ∗ ∗ ∗ ∗ 190 [0] [0] Entry 1: Partition/ Enable Partition/ Sound Enable VISTA-20P: Enter partition in which the keypad is located where: Entry 1 - Partition/Enable: Enter the desired option for the keypad’s For Touchscreen device usage home partition.
  • Page 18: Configurable Zone Types Worksheet

    CONFIGURABLE ZONE TYPES WORKSHEET Configurable zone types 90 and 91 can be programmed via downloader software or from a keypad using data fields*182- *185. Configurable zone types 92 and 93 (VISTA-20P only) can only be programmed using the downloader software. Programming Configurable Zone Type options involves making 10 entries in data field *182 for zone type 90 and field *184 for zone type 91, where each entry represents the sum of the values of the various options shown in the tables below.
  • Page 19: Zone Programming Menu Mode

    ∗ ∗ ∗ ∗ 56 ZONE PROGRAMMING MENU MODE (press *56 while in Program mode) The Zone Programming Worksheet is on page 44. Zones and Partitions Each protection zone needs to be programmed with various attributes using *56 Zone Programming mode or , 58 Expert Programming Mode.
  • Page 20 Report Code (RC) Enter the report code for this zone, which consists of 2 10 Report Code hexadecimal digits, each in turn consisting of 2 numerical digits. First Digit: 1-9, 10 for 0, 11 for 1st 01 2nd 00 For example, for a report code of “10,” enter 01 and 00 . B, 12 for C, 13 for D, 14 for E, For Contact ID®, entering any non-zero entry as the first digit 15 for F...
  • Page 21: Expert Zone Program Mode

    ∗ ∗ ∗ ∗ 58 EXPERT ZONE PROGRAM MODE (press ∗ ∗ ∗ ∗ 58 while in Data Programming mode) This method is designed for use by installers with previous experience in programming HONEYWELL control panels. This mode is also used to program wireless keys using pre-defined templates.
  • Page 22: Wireless Key Programming Templates

    Zone Programming A summary screen with the selected zone’s current Zn ZT P RC IN: L programming appears. ZT = see Zone Type chart 00 1 10 RF 1 Begin programming zone information as follows: shown in *56 Menu • Enter Zone Type (ZT), Partition (P), Report Code (RC; 0-9 Mode “Zone Type”...
  • Page 23 Confirm • If “Yes” was entered at the SET TO CONFIRM? prompt XMIT TO CONFIRM previously (see first prompt following entry into the ∗58 [∗] to continue PRESS TO SKIP Expert Programming Mode), the display on the left will appear. Confirm serial and loop numbers by activating the wireless key.
  • Page 24: Function Key Programming Menu Mode

    ∗ ∗ ∗ ∗ 57 FUNCTION KEY PROGRAMMING MENU MODE (press ∗ ∗ ∗ ∗ 57 while in Data Programming mode) The Function Key Worksheet is on page 45. The system provides the ability to program each of the four keypad function keys to perform one of 12 system operations. The end user can then activate the function by simply pressing and holding the programmed key for 2 seconds.
  • Page 25: Output Device Programming General Information (*79/*80 Menu Mode)

    OUTPUT DEVICE PROGRAMMING GENERAL INFORMATION (*79/*80 Menu Mode) Output Devices: The VISTA-20P system supports up to 16 relays and/or Powerline Carrier devices (X-10 devices) plus 2 built-in trigger outputs in any combination. These 18 “outputs” are assigned to system-wide output numbers (01-18). Use *79 Menu Mode to assign output numbers and map them to device addresses.
  • Page 26: Output Function Menu Mode

    Output Type Select whether this is a relay or a Powerline Carrier (X-10) XX OUTPUT TYPE device. 0 = delete DELETE If Powerline Carrier Device (X-10) is selected, go to “A” prompt. 1 = relay on 4204/4229 If relay is selected, skip to “B” prompt. 2 = Powerline Carrier Device [∗] to continue “A”...
  • Page 27 80 Menu Mode Output Function No. Enter the output function number to be defined (or 00 to exit) Output Funct. # (VISTA-20P: 01-48 (00 = Quit) (VISTA-15P: 01-24) [∗] to continue; 00 to quit Summary Screen This screen displays a summary of the current output A E P Trig programming (for this example, Zone List has been selected-this is [∗] to continue...
  • Page 28: Zone List Menu Mode

    Zone Number (prompt appears if zone number was selected) “C” Enter the desired zone number associated with this output Press [ , ] to continue. 01 Enter Zn No. number. At the ENTER EVENT prompt, enter the zone event that will activate this output. 01 Enter Event 0 = restore;...
  • Page 29: Alpha Descriptor Menu Mode

    Deleting a Zone To save the zone list, enter 0 and the system returns to the Zone 01 Delete Zone? List No. prompt. 0 = don’t delete zones 0 = No 1 = Yes To delete a zone or zones in a zone list, enter 1 to continue. 1 = go to next prompt to delete zones [∗] to continue...
  • Page 30 Descriptor Example EXAMPLE: “BACK DOOR” EXAMPLE: a. From the list, BACK = 013, so, after entering the zone number to be edited (step 1), enter #013. If you accidentally enter the wrong word, simply press [#] plus the correct 3-digit number for Z N 0 1 B A C K the word you want.
  • Page 31: Alpha Vocabulary List (For Entering Zone Descriptors)

    ALPHA VOCABULARY LIST (For Entering Zone Descriptors) (Word Space) • 057 DOOR ∗ ∗ ∗ ∗ – L – – R – – V – – A – • 106 LAUNDRY ∗ ∗ ∗ ∗ RADIO VALVE • 059 DOWN •...
  • Page 32: Setting Schedules

    SETTING SCHEDULES (Installer Code + [#] + [6] [4]) The system provides schedules, which can be used to automatically control 11 types of system events at pre-defined times. Some events are reserved for the installer only. VISTA-20P: Provides up to 32 schedules: 16 schedules for use by the end-user, 16 for use by the installer. VISTA-15P: Provides up to 8 schedules: 4 schedules for use by the end user, 4 for use by the installer.
  • Page 33: Avs System Enable And Quick Programming Commands

    Repeat Option Enter the desired repeat option for this schedule. R E P E A T O P T I O N e.g., To make a schedule that happens everyday you would 0 = do not repeat 0 - 4 select all days with a repeat count of 1.
  • Page 34: Communication Device Menu Mode (Pass-Through Programming)

    ∗ ∗ ∗ ∗ 29 COMMUNICATION DEVICE MENU MODE (Pass-Through Programming) This mode is for programming an IP, GSM, or IP/GSM Communicator Module using an alpha keypad. Alternatively, these options can be programmed via the AlarmNet Direct website. After programming is complete, the module must be registered with AlarmNet before reporting via the communication device can occur.
  • Page 35: Uploading/Downloading Via The Internet

    Registering the Communication Device with AlarmNet The communication device must be registered with AlarmNet before internet communication (via IP or GSM) can occur. Register Using the Alpha Keypad and ∗ ∗ ∗ ∗ 29 Menu Mode 1. Enter *29 Menu mode, select Diagnostic mode, then press Shift then [↑] key (D key followed by the B key). The registration message is sent (“Registering”...
  • Page 36: Zone Type Definitions

    ZONE TYPE DEFINITIONS Zone types define the way in which the system responds to faults in each zone. Type 00 Zone Not Used Type 12 Monitor Zone Program a zone with this zone type if the zone is not used. •...
  • Page 37: Report Code Formats

    REPORT CODE FORMATS The following table describes the communication formats. FORMAT TYPE DESCRIPTION 3+1 and 4+1 Comprises a 3- (or 4-) digit subscriber number and a single-digit report code (e.g., Alarm, Standard Formats Trouble, Restore, Open, Close, etc). Ex. SSS(S) A S = Subscriber ID;...
  • Page 38: System Security Codes

    SYSTEM SECURITY CODES The systems provides one Installer code, one System Master code, plus a set of other user codes intended for other users of the system. These codes can each be assigned one of 5 authority levels, which determine the functions each code can perform as listed in the table below.
  • Page 39: Keypad Functions

    KEYPAD FUNCTIONS The following is a brief list of system commands. For detailed information concerning system functions, refer to the User's Manual. For Touch Screen style keypad users, refer to the separate Touch Screen keypad (AUI) User’s Guide. Keypad Commands Function Description Silence Burglary Alarms...
  • Page 40: Various System Trouble Displays

    VARIOUS SYSTEM TROUBLE DISPLAYS Alpha Display Fixed Disp. Meaning ALARM CANCELED Will appear if an exit or interior zone contained a fault during closing at the time the Exit Delay ended (e.g., exit door left open), but the system was disarmed during the Entry Delay time.
  • Page 41: Ul Notices

    UL NOTICES 1. Entry Delay No. 1 and No. 2 (fields ∗ 35, ∗ 36) cannot be greater than 30 seconds for UL Residential Burglar Alarm installations, and entry delay plus dial delay should not exceed 1 minute. For UL Commercial Burglar Alarm installations, total entry delay may not exceed 45 seconds.
  • Page 42: Fcc Statements

    FCC STATEMENTS FEDERAL COMMUNICATIONS COMMISSION (FCC) Part 15 The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or User's Manual. Unauthorized changes or modifications could void the user's authority to operate the equipment. CLASS B DIGITAL DEVICE STATEMENT This equipment has been tested to FCC requirements and has been found acceptable for use.
  • Page 43: Limitations Statement

    • Note the proper model number of this product, and the version level (if known) along with any documentation that came with the product. • Note your Honeywell customer number and/or company name. Having this information handy will make it easier for us to serve you quickly and effectively.
  • Page 44: Worksheet For ∗ ∗ ∗ ∗ 56 Zone Programming

    WORKSHEET for ∗ ∗ ∗ ∗ 56 ZONE PROGRAMMING (VISTA-15P supports up to 32 zones: 1-6, 9-34, 49-56) [default shown in brackets] Zone Zn Type Part. Report Hardwire Rsp. Time Location Type [09] [EOL] [01] [EOL] [03] [EOL] [03] [EOL] [03] [EOL] [03]...
  • Page 45: Worksheet For ∗ ∗ ∗ ∗ 57 Function Key Programming

    WORKSHEET for ∗ ∗ ∗ ∗ 57 FUNCTION KEY PROGRAMMING Comments Option Function P1 P2 P1 P2 P1 P2 P1 P2 Paging Time Display Arm AWAY Arm STAY Arm NIGHT-STAY Step Arming Device Activation Device: Comm. Test Macro Key 1 Assign each macro key to only a single partition.
  • Page 46: W Orksheet For ∗ ∗ ∗ ∗ 80 Output Function Programming

    W ORKSHEET for ∗ ∗ ∗ ∗ 80 OUTPUT FUNCTION PROGRAMMING Fill in the required data on the worksheet below and follow the programming procedure in the installation manual as you enter the data during the displays and prompts that appear in sequence. Notes: 1.
  • Page 47: Worksheet For Schedules

    WORKSHEET for SCHEDULES (installer code + [#] + [6] [4]; master code can only access schedules 01-16 for VISTA-20P, 01-04 for VISTA-15P, and events 00-07 for both controls; VISTA-15P supports up to 8 schedules, VISTA-20P supports up to 32 schedules ) Event Device No.
  • Page 48: 5800 Series Transmitter Input Loop Identification

    ENROLL AS "RF" ENROLL AS "RF" WARRANTY INFORMATION For the latest warranty information, please go to: www.honeywell.com/security/hsc/resources/wa 2 Corporate Center Drive, Suite 100 P.O. Box 9040, Melville, NY 11747 Copyright © 2003 Honeywell International Inc. www.honeywell.com/security ÊK5305-1PRV8wŠ K5305-1PRV8 5/11 Rev. A...

Table of Contents