Display
Description
LSENS
Indicates a smoke detector with a low sensitivity level. The detector may not detect a smoke condition. The
detector should be cleaned or replaced.
RCVR
Indicates the system has more wireless zones programmed than the RF receiver can support. If this is not
SETUP
corrected, none of the zones in the system will be protected. If additional wireless zones are desired, use an
ERROR
appropriate receiver.
MODEM
This indicates that the control is on-line with a remote computer.
COMM
System Off-Normal Report
If programmed, an Off-Normal report is generated instead of the periodic test report if any of the following conditions
are present at the time of the report:
Fire trouble on any zone (zone types 9, 16, 17, 18)
Fire supervisory present (zone type 18)
Unrestored fire alarm on any zone
Bypass of any fire zone
A fault for any supervised fire Notification Appliance Circuit
Bypass/disable of any supervised fire Notification Appliance Circuit
Telco fault of either dialer line
Bypass/disable of either dialer line
Earth ground fault
Bypass of earth ground supervisory zone
Fault on LORRA "XMIT OK" signal (if enabled)
LORRA trigger bypassed
AC failure
Low system battery
Keypad supervision fault
The Off-Normal report is sent as follows:
Contact ID: Code 608
Express Speed: Digits programmed in System Group #4 report codes

To the Installer

Regular maintenance and inspection (at least annually) by the installer and frequent testing by the user are vital to
continuous satisfactory operation of any alarm system.
The installer should assume the responsibility of developing and offering a regular maintenance program to the user as
well as acquainting the user with the proper operation and limitations of the alarm system and its component parts.
Recommendations must be included for a specific program of frequent testing (at least weekly) to ensure the system's
proper operation at all times.
Turning the System over to the User
Fully explain the operation of the system to the user by going over each of its functions, as well as the User Guide
supplied.
In particular, explain the operation of each zone (entry/exit, perimeter, interior, fire, etc.). Be sure the user understands
how to operate any emergency feature(s) programmed into the system.