Honeywell VISTA-32FBPT Installation And Setup Manual page 54

Commercial fire and burglary partitioned security system with scheduling
Hide thumbs Also See for VISTA-32FBPT:
Table of Contents

Advertisement

1.
In Worksheet 1, enter devices used on the polling loop. Calculate total current draw on the polling loop.
Worksheet 1: Total Polling Loop Current Draw
Polling Loop Device
(terminals 28 & 29 – 128mA) *
*The total current cannot exceed 128mA. If total load exceeds 128mA, then a 4297 Loop Extender Module can be used. This module is
powered from the panel's auxiliary power, and provides a separate polling loop output, which can support an additional 128mA load.
Note that the total number of points connected to the panel cannot exceed 119.
2.
In Worksheet 2, enter devices used on Auxiliary Power 1. Calculate standby and alarm currents, then add to get
Auxiliary Power 1 current subtotal.
Worksheet 2: Auxiliary Power 1 Current Load
Device
Device Current X
Model #
# of Units
Auxiliary Power 1 Subtotal
(terminals 10 & 11)
Current
# of Units
Polling Loop Subtotal
Total Current
Standby
Alarm
.
1A max
(for Canada
650mA)
1.7A max.
Total
54