6.2 STATUS
For form-A contact outputs, the state of the voltage and current detectors is displayed as Off, VOff, IOff, On, IOn,
and VOn. For form-C contact outputs, the state is displayed as Off or On.
NOTE
PATH: ACTUAL VALUES
VIRTUAL OUTPUTS
The present state of up to 96 virtual outputs is shown here. The first line of a message display indicates the ID of the virtual
output. For example, 'Virt Op 1' refers to the virtual output in terms of the default name-array index. The second line of the
display indicates the logic state of the virtual output, as calculated by the FlexLogic equation for that output.
PATH: ACTUAL VALUES
AUTORECLOSE 1
The automatic reclosure shot count is shown here.
6
a) STATUS
PATH: ACTUAL VALUES
REMOTE DEVICES
STATUS
The present state of the programmed remote devices is shown here. The
whether or not all programmed remote devices are online. If the corresponding state is "No", then at least one required
remote device is not online.
6-6
STATUS
VIRTUAL OUTPUTS
Virt Op
Off
Virt Op
MESSAGE
Off
Virt Op 96
MESSAGE
Off
STATUS
AUTORECLOSE
AUTORECLOSE 1
SHOT COUNT:
STATUS
REMOTE DEVICES STATUS
All REMOTE DEVICES
ONLINE: No
REMOTE DEVICE
MESSAGE
STATUS: Offline
REMOTE DEVICE
MESSAGE
STATUS: Offline
REMOTE DEVICE 16
MESSAGE
STATUS: Offline
F35 Multiple Feeder Protection System
Range: On, Off
1
Range: On, Off
2
↓
Range: On, Off
AUTORECLOSE 1(6)
Range: 0, 1, 2, 3, 4
0
Range: Yes, No
Range: Online, Offline
1
Range: Online, Offline
2
↓
Range: Online, Offline
ALL REMOTE DEVICES ONLINE
6 ACTUAL VALUES
6.2.7 VIRTUAL OUTPUTS
6.2.8 AUTORECLOSE
6.2.9 REMOTE DEVICES
message indicates
GE Multilin