Advertisement

5 SETTINGS
b) VOLTAGE BANKS

PATH: SETTINGS
SYSTEM SETUP
 VOLTAGE BANK F5
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
Because energy parameters are accumulated, these values should be recorded and then reset
immediately prior to changing VT characteristics.
Three banks of phase/auxiliary VTs can be set, where voltage banks are denoted in the following format (X represents the
module slot position letter):
Xa, where X = {F, M, U} and a = {5}.
See the Introduction to AC Sources section at the beginning of this chapter for additional details.
With VTs installed, the relay can perform voltage measurements as well as power calculations. Enter the
made to the system as "Wye" or "Delta". An open-delta source VT connection would be entered as "Delta".
NECTION
The nominal
PHASE VT F5 SECONDARY
voltage is applied to the VT primary.
NOTE
For example, on a system with a 13.8 kV nominal primary voltage and with a 14400:120 volt VT in a delta connec-
tion, the secondary voltage would be 115; that is, (13800 / 14400) × 120. For a wye connection, the voltage value
entered must be the phase to neutral voltage which would be 115 /
On a 14.4 kV system with a delta connection and a VT primary to secondary turns ratio of 14400:120, the voltage
value entered would be 120; that is, 14400 / 120.
If the
PHASE VT F5 CONNECTION
NOTE

PATH: SETTINGS
SYSTEM SETUP
 POWER SYSTEM
MESSAGE
MESSAGE
MESSAGE
GE Multilin

AC INPUTS
VOLTAGE BANK F5(U5)
PHASE VT F5
CONNECTION: Wye
PHASE VT F5
SECONDARY: 66.4 V
PHASE VT F5
RATIO: 1.00 :1
AUXILIARY VT F5
CONNECTION: Vag
AUXILIARY VT F5
SECONDARY: 66.4 V
AUXILIARY VT F5
RATIO: 1.00 :1
voltage setting is the voltage across the relay input terminals when nominal
is set to "Delta", the relay will not calculate voltage harmonics.


POWER SYSTEM

NOMINAL FREQUENCY:
60 Hz
PHASE ROTATION:
ABC
FREQUENCY AND PHASE
REFERENCE: SRC 1
FREQUENCY TRACKING:
Enabled
F35 Multiple Feeder Protection System
5.4 SYSTEM SETUP
Range: Wye, Delta
Range: 25.0 to 240.0 V in steps of 0.1
Range: 1.00 to 24000.00 in steps of 0.01
Range: Vn, Vag, Vbg, Vcg, Vab, Vbc, Vca
Range: 25.0 to 240.0 V in steps of 0.1
Range: 1.00 to 24000.00 in steps of 0.01
3
= 66.4.
5.4.2 POWER SYSTEM
Range: 25 to 60 Hz in steps of 1
Range: ABC, ACB
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
Range: Disabled, Enabled
5
PHASE VT F5 CON-
5-103