GE UR F35 Series Instruction Manual page 176

Multiple feeder protection system
Hide thumbs Also See for UR F35 Series:
Table of Contents

Advertisement

5.2 PRODUCT SETUP
The main reception menu is applicable to configurable GOOSE only and contains the configurable GOOSE dataset items
for reception:
PATH: SETTINGS
PRODUCT SETUP

RECEPTION
CONFIGURABLE GOOSE
 CONFIG GSE 1
 DATASET ITEMS
The configurable GOOSE settings allow the F35 to be configured to receive a number of different datasets within IEC
61850 GOOSE messages. Up to sixteen different configurable datasets can be configured for reception. This is useful for
intercommunication between F35 IEDs and devices from other manufacturers that support IEC 61850.
For intercommunication between F35 IEDs, the fixed (DNA/UserSt) dataset can be used. The DNA/UserSt dataset contains
the same DNA and UserSt bit pairs that are included in GSSE messages.
To set up a F35 to receive a configurable GOOSE dataset that contains two IEC 61850 single point status indications, the
following dataset items can be selected (for example, for configurable GOOSE dataset 1): "GGIO3.ST.Ind1.stVal" and
5
"GGIO3.ST.Ind2.stVal". The F35 will then create a dataset containing these two data items. The Boolean status values from
these data items can be utilized as remote input FlexLogic operands. First, the
be set to contain dataset "GOOSEIn 1" (that is, the first configurable dataset). Then
set to "Dataset Item 1" and "Dataset Item 2". These remote input FlexLogic operands will then change state in accordance
with the status values of the data items in the configured dataset.
Double-point status values may be included in the GOOSE dataset. Received values are populated in the
GGIO3.ST.IndPos1.stVal and higher items.
Floating point analog values originating from MMXU logical nodes may be included in GOOSE datasets. Deadband (non-
instantaneous) values can be transmitted. Received values are used to populate the GGIO3.MX.AnIn1 and higher items.
Received values are also available as FlexAnalog parameters (GOOSE analog In1 and up).
GGIO3.MX.AnIn1 to GGIO3.MX.AnIn32 can only be used once for all sixteen reception datasets.
NOTE
5-48

COMMUNICATIONS
CONFIGURABLE GOOSE 1(16)
ITEM
1:
GGIO3.ST.Ind1.stVal
ITEM
2:
MESSAGE
GGIO3.ST.IndPos1.stV
ITEM
3:
MESSAGE
None
ITEM 32:
MESSAGE
None
F35 Multiple Feeder Protection System

IEC 61850 PROTOCOL

CONFIG GSE 1(32) DATA ITEMS
Range: all valid MMS data item references for
transmitted data
Range: all valid MMS data item references for
transmitted data
Range: all valid MMS data item references for
transmitted data
Range: all valid MMS data item references for
transmitted data
REMOTE DEVICE 1(16) DATASET
REMOTE IN 1(16) ITEM
5 SETTINGS
GSSE/GOOSE CONFIGURATION
setting must
settings must be
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents