GE UR F35 Series Instruction Manual page 534

Multiple feeder protection system
Hide thumbs Also See for UR F35 Series:
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Bitmask
Value
29
DNA-29
30
DNA-30
31
DNA-31
32
DNA-32
33
UserSt-1
34
UserSt-2
B
F157
ENUMERATION: BREAKER MODE
0 = 3-Pole, 1 = 1-Pole
F166
ENUMERATION: AUXILIARY VT CONNECTION TYPE
0 = Vn, 1 = Vag, 2 = Vbg, 3 = Vcg, 4 = Vab, 5 = Vbc, 6 = Vca
F167
ENUMERATION: SIGNAL SOURCE
0 = SRC 1, 1 = SRC 2, 2 = SRC 3, 3 = SRC 4,
4 = SRC 5, 5 = SRC 6
F172
ENUMERATION: SLOT LETTERS
Bitmas
Slot
Bitmas
k
k
0
F
4
1
G
5
2
H
6
3
J
7
F173
ENUMERATION: DCmA INPUT/OUTPUT RANGE
Bitmask
DCmA input/output range
0
0 to –1 mA
1
0 to 1 mA
2
–1 to 1 mA
3
0 to 5 mA
4
0 to 10 mA
5
0 to 20 mA
6
4 to 20 mA
B-80
Bitmask
Value
64
UserSt-32
65
Dataset Item 1
66
Dataset Item 2
67
Dataset Item 3
96
Dataset Item 32
Slot
Bitmas
Slot
Bitmas
k
k
K
8
P
12
L
9
R
13
M
10
S
14
N
11
T
15
F35 Multiple Feeder Protection System
F174
ENUMERATION: TRANSDUCER RTD INPUT TYPE
0 = 100 Ohm Platinum, 1 = 120 Ohm Nickel,
2 = 100 Ohm Nickel, 3 = 10 Ohm Copper
F177
ENUMERATION: COMMUNICATION PORT
0 = None, 1 = COM1-RS485 (not applicable to UR firmware 7.00),
2 = COM2-RS485, 3 = Front Panel-RS232, 4 = Network - TCP,
5 = Network - UDP
F183
ENUMERATION: AC INPUT WAVEFORMS
Bitmask
Definition
0
Off
1
8 samples/cycle
2
16 samples/cycle
3
32 samples/cycle
4
64 samples/cycle
F184
ENUMERATION: IEC GOOSE DATASET
Value
IEC 61850 dataset
0
Off
Slot
1
GooseIn 1
2
GooseIn 2
U
3
GooseIn 3
V
4
GooseIn 4
W
5
GooseIn 5
X
6
GooseIn 6
7
GooseIn 7
8
GooseIn 8
9
GooseIn 9
10
GooseIn 10
11
GooseIn 11
12
GooseIn 12
13
GooseIn 13
14
GooseIn 14
15
GooseIn 15
16
GooseIn 16
F186
ENUMERATION: MEASUREMENT MODE
0 = Phase to Ground, 1 = Phase to Phase
APPENDIX B