GE UR F35 Series Instruction Manual page 151

Multiple feeder protection system
Hide thumbs Also See for UR F35 Series:
Table of Contents

Advertisement

5 SETTINGS
Role — 16 bit unsigned, of type format F617
ENUMERATION
ROLE
0
None
1
Administrator
2
Supervisor
3
Engineer
4
Operator
5
Factory
Activity Value — 16 bit unsigned
ENUMERATION
DESCRIPTION
1
Authentication Failed
2
User Lockout
3
FW Upgrade
4
FW Lock
5
Settings Lock
6
Settings Change. Because this can fill the entire event log, it is supported by the
already existing Settings_Change.log file. This event is not required.
7
Clear Oscillography command
8
Clear Data Logger command (not applicable to all UR products)
9
Clear Demand Records command (not applicable to all UR products)
10
Clear Energy command (not applicable to all UR products)
11
Clear Unauthorized Access command
12
Clear Teleprotection Counters command (not applicable to all UR products)
13
Clear All Relay Records command
14
Role Log in
15
Role Log off
The following events are recorded in the syslog.
Table 5–3: SYSTEM EVENTS RECORDED
EVENT
FAILED_AUTH, ORIGIN,
TIMESTAMP
AUTH_LOCKOUT, ORIGIN,
TIMESTAMP
FIRMWARE_UPGD, ORIGIN,
TIMESTAMP
FIRMWARE_LOCK, ORIGIN,
TIMESTAMP
SETTING_CHG, ORIGIN,
TIMESTAMP
SETTING_LOCK, ORIGIN,
TIMESTAMP
LOGIN, ORIGIN, TIMESTAMP
LOGOUT, ORIGIN, TIMESTAMP
CLEAR_OSCILLOGRAPHY
CLEAR_DATA_LOGGER
CLEAR_DEMAND_RECS
CLEAR_ENERGY
RESET_UNAUTH_ACCESS
CLEAR_TELEPROTECTION_CNT
CLEAR_ALL_RECS
GE Multilin
SEVERITY
DESCRIPTION
Warning (4)
A failed authentication with origin information (username and IP:MAC
address), a time stamp in UTC time when it occurred
Error (3)
An authentication lockout has occurred because of too many failed
authentication attempts
Warning (4)
Indicates that a change of firmware has occurred
Critical (1)
An attempt was made to change firmware while the firmware lock was
enabled
Notice (5)
Indicates setting change(s)
Critical (1)
An attempt was made to change settings while the settings lock was enabled
Warning (4)
Indicates when a certain role logged in
Notice (5)
Indicates when a certain role logged out or timed out
Notice (5)
Clear oscillography command was issued
Notice (5)
Clear data logger command was issued
Notice (5)
Clear demand records command was issued
Notice (5)
Clear energy command was issued
Warning (4)
Reset Unauthorized access command was issued
Notice (5)
Clear teleprotection counters command was issued
Warning (4)
Clear all records command was issued
F35 Multiple Feeder Protection System
5.2 PRODUCT SETUP
5
5-23

Advertisement

Table of Contents
loading

Table of Contents