Modbus User Map; Real Time Clock - GE UR F35 Series Instruction Manual

Multiple feeder protection system
Hide thumbs Also See for UR F35 Series:
Table of Contents

Advertisement

5 SETTINGS
DESCRIPTION
VALUE
Virtual Input 1
1
Virtual Input 2
2
...
Virtual Input 64
64
PATH: SETTINGS
PRODUCT SETUP
 MODBUS USER MAP
MESSAGE
MESSAGE
MESSAGE
The Modbus user map provides read-only access for up to 256 registers. To obtain a memory map value, enter the desired
address in the
line (converted from hex to decimal format). The corresponding value displays in the
ADDRESS
value of "0" in subsequent register
by "1". An address value of "0" in the initial register means "none" and values of "0" display for all registers. Different
values can be entered as required in any of the register positions.
ADDRESS
a) MAIN MENU
PATH: SETTINGS
PRODUCT SETUP
 REAL TIME
 CLOCK
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The relay contains a real time clock (RTC) to create timestamps for communications protocols as well as for historical data,
such as event records and oscillography. When the relay restarts, the RTC initializes from an onboard battery-backed
clock, which has the same accuracy as an electronic watch, approximately ±1 minute per month (~23 ppm). Once the RTC
is synchronized with the Precision Time Protocol (PTP), IRIG-B, or SNTP, its accuracy approaches that of the synchroniz-
ing time delivered to the relay. While the RTC is not synchronized via PTP or IRIG-B, or the relay determines than it has an
offset possibly greater than 10 µs from the international time standard, the CLOCK UNSYNCHRONIZED FlexLogic oper-
and is activated.
The
SYNCHRONIZING SOURCE
ures the priority sequence of the time synchronization source, to determine which of the available external time sources to
use for time synchronization. A setting of None causes the RTC and the synchrophasor clock to free-run until the clock is
GE Multilin


MODBUS USER MAP

ADDRESS
1:
VALUE:
0
ADDRESS
2:
VALUE:
0
ADDRESS
3:
VALUE:
0
ADDRESS 256:
VALUE:
0
lines automatically returns values for the previous
ADDRESS


REAL TIME CLOCK

SYNCRONIZING SOURCE:
None
REAL TIME CLOCK
EVENTS: Disabled
IRIG-B SIGNAL TYPE:
None
 PRECISION TIME
 PROTOCOL (1588)
 SNTP PROTOCOL
 LOCAL TIME
setting displays when the relay includes the IEEE 1588 software option. The setting config-
F35 Multiple Feeder Protection System
Range: 0 to 65535 in steps of 1
0
Range: 0 to 65535 in steps of 1
0
Range: 0 to 65535 in steps of 1
0
Range: 0 to 65535 in steps of 1
0
Range: None, PP/IRIG-B/PTP/SNTP, IRIG-B/PP/PTP/
SNTP, PP/PTP/IRIG-B/SNTP
Range:Enabled, Disabled
Range:None, DC Shift, Amplitude Modulated
See below
See below
See below
5.2 PRODUCT SETUP
5.2.5 MODBUS USER MAP
line. A
VALUE
lines incremented
ADDRESS
5.2.6 REAL TIME CLOCK
5-65