5.6 GROUPED ELEMENTS
e) AUXILIARY OVERVOLTAGE (ANSI 59X, IEC PTOV)
PATH: SETTINGS
GROUPED ELEMENTS
AUXILIARY OV1
The F35 contains one auxiliary overvoltage element for each VT bank. This element is intended for monitoring overvoltage
5
conditions of the auxiliary voltage. The nominal secondary voltage of the auxiliary voltage channel entered under
SETUP
AC INPUTS
pickup level.
5-168
SETTING GROUP 1(6)
AUX OV1
FUNCTION: Disabled
AUX OV1 SIGNAL
MESSAGE
SOURCE: SRC 1
AUX OV1 PICKUP:
MESSAGE
0.300 pu
AUX OV1 PICKUP
MESSAGE
DELAY: 1.00 s
AUX OV1 RESET
MESSAGE
DELAY: 1.00 s
AUX OV1 BLOCK:
MESSAGE
Off
AUX OV1 TARGET:
MESSAGE
Self-reset
AUX OV1 EVENTS:
MESSAGE
Disabled
VOLTAGE BANK X5
AUXILIARY VT X5 SECONDARY
Figure 5–68: AUXILIARY OVERVOLTAGE SCHEME LOGIC
F35 Multiple Feeder Protection System
VOLTAGE ELEMENTS
AUXILIARY OV1(3)
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
Range: 0.000 to 3.000 pu in steps of 0.001
Range: 0.00 to 600.00 s in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
Range: FlexLogic operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
is the per-unit (pu) base used when setting the
5 SETTINGS
SYSTEM
GE Multilin