5.2 PRODUCT SETUP
a = 0.0068
Since the step is in increments of 0.001, we round it at:
a = 0.006
b = -4096
Vt = 0.006 * V - 4096
For max voltage 500000V * 2.4 = 1200000V, we transmit
Vt = 0.006 * 1200000 - 4096 = 7200 - 4096 = 3104
PATH: SETTINGS
PRODUCT SETUP
IEC103 COMMANDS
COMMAND 0
5
COMMAND 31
Commands are received as General Command (Type Identification 20). The user can configure which action to perform
when an ASDU command comes.
A list of available mappings is provided on the F35. This includes 64 virtual inputs (see the following table). The ON and
OFF for the same ASDU command can be mapped to different virtual inputs.
Each command is identified by the unique combination made by the function type (FUN), and information number (INF). If
the master sends an ASDU command that does not have the FUN and INF of any configured command, the relay rejects it.
Table 5–8: COMMANDS MAPPING TABLE
DESCRIPTION
Off
0
5-64
COMMUNICATIONS
COMMAND 0
COMMAND 1
MESSAGE
COMMAND 31
MESSAGE
COMMAND 0 FUN:
0
COMMAND 0 INF:
MESSAGE
0
COMMAND 0 ON:
MESSAGE
Off
COMMAND 0 OFF:
MESSAGE
Off
COMMAND 31 FUN:
0
COMMAND 31 INF:
MESSAGE
0
COMMAND 31 ON:
MESSAGE
Off
COMMAND 31 OFF:
MESSAGE
Off
VALUE
F35 Multiple Feeder Protection System
IEC60870-5-103
IEC103 COMMANDS
Range: see sub-menu below
Range: see sub-menu below
↓
Range: see sub-menu below
Range: 0 to 255 in steps of 1
Range: 0 to 255 in steps of 1
Range: Virtual input
Range: Virtual input
↓
Range: 0 to 255 in steps of 1
Range: 0 to 255 in steps of 1
Range: Virtual input
Range: Virtual input
5 SETTINGS
GE Multilin