GE UR F35 Series Instruction Manual page 499

Multiple feeder protection system
Hide thumbs Also See for UR F35 Series:
Table of Contents

Advertisement

APPENDIX B
Table B–10: MODBUS MEMORY MAP (Sheet 37 of 64)
ADDR
REGISTER NAME
7F0A
Reserved (7 items)
7F11
...Repeated for Neutral Overvoltage 2
7F22
...Repeated for Neutral Overvoltage 3
Auxiliary Undervoltage (Read/Write Grouped Setting (3 modules)
7F60
Auxiliary Undervoltage 1 Function
7F61
Auxiliary Undervoltage 1 Signal Source
7F62
Auxiliary Undervoltage 1 Pickup
7F63
Auxiliary Undervoltage 1 Delay
7F64
Auxiliary Undervoltage 1 Curve
7F65
Auxiliary Undervoltage 1 Minimum Voltage
7F66
Auxiliary Undervoltage 1 Block
7F68
Auxiliary Undervoltage 1 Target
7F69
Auxiliary Undervoltage 1 Events
7F6A
Reserved (7 items)
7F71
...Repeated for Auxiliary Undervoltage 2
7F82
...Repeated for Auxiliary Undervoltage 3
Auxiliary Overvoltage (Read/Write Grouped Setting) (3 modules)
7FA0
Auxiliary Overvoltage 1 Function
7FA1
Auxiliary Overvoltage 1 Signal Source
7FA2
Auxiliary Overvoltage 1 Pickup
7FA3
Auxiliary Overvoltage 1 Pickup Delay
7FA4
Auxiliary Overvoltage 1 Reset Delay
7FA5
Auxiliary Overvoltage 1 Block
7FA7
Auxiliary Overvoltage 1 Target
7FA8
Auxiliary Overvoltage 1 Events
7FA9
Reserved (8 items)
7FB1
...Repeated for Auxiliary Overvoltage 2
7FC2
...Repeated for Auxiliary Overvoltage 3
Frequency (Read Only)
8000
Tracking Frequency
Temp Monitor Actual Values (Read Only Non-Volatile)
81C0
Reserved Register T1
81C1
Reserved Register T2
81C2
Reserved Register T3
81C4
Reserved Register T4
81C6
Reserved Register T5
81C8
Reserved Register T6
81CA
Reserved Register T7
81CC
Reserved Register T8
(8-bit) Switch (Read/Write Setting) (6 modules)
82C0
Switch 1 Function
82C1
Switch 1 Argument A Bits (8 items)
82D1
Switch 1 Argument B Bits (8 items)
82E1
Switch 1 Control
82E3
Reserved (6 items)
82E9
...Repeated for Switch 2
8312
...Repeated for Switch 3
833B
...Repeated for Switch 4
8364
...Repeated for Switch 5
838D
...Repeated for Switch 6
EGD Fast Production Status (Read Only Non-Volatile and Read Only)
83E0
EGD Fast Producer Exchange 1 Signature
83E1
EGD Fast Producer Exchange 1 Configuration Time
GE Multilin
RANGE
0 to 65535
0 to 1
0 to 5
0 to 3
0 to 600
0 to 1
0 to 3
0 to 4294967295
0 to 2
0 to 1
0 to 65535
0 to 1
0 to 5
0 to 3
0 to 600
0 to 600
0 to 4294967295
0 to 2
0 to 1
0 to 65535
2 to 90
-55 to 125
-55 to 125
-2147483647 to
2147483647
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 1
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 65535
0 to 65535
0 to 4294967295
F35 Multiple Feeder Protection System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
---
1
F111
0 (Definite Time)
pu
0.001
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
Hz
0.01
F001
C
1
F002
C
1
F002
---
1
F004
---
1
F003
---
1
F003
---
1
F003
---
1
F003
---
1
F003
---
1
F102
---
1
F300
---
1
F300
---
1
F300
---
1
F001
---
1
F001
---
---
F003
DEFAULT
0
0 (Disabled)
B
0 (SRC 1)
700
100
100
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
300
100
100
0
0 (Self-reset)
0 (Disabled)
0
0
-55
125
0
0
0
0
0
0
0 (Disabled)
0
0
0
0
0
0
B-45

Advertisement

Table of Contents
loading

Table of Contents