User-Programmable Leds - GE UR F35 Series Instruction Manual

Multiple feeder protection system
Hide thumbs Also See for UR F35 Series:
Table of Contents

Advertisement

5.2 PRODUCT SETUP
The 90% thermal response time characteristic of 15 minutes is illustrated below. A setpoint establishes the time to reach
90% of a steady-state value, just as the response time of an analog instrument. A steady state value applied for twice the
response time will indicate 99% of the value.
CALCULATION METHOD 2: BLOCK INTERVAL
This method calculates a linear average of the quantity (RMS current, real power, reactive power, or apparent power) over
the programmed demand time interval, starting daily at 00:00:00 (i.e. 12:00 am). The 1440 minutes per day is divided into
the number of blocks as set by the programmed time interval. Each new value of demand becomes available at the end of
each time interval.
CALCULATION METHOD 2a: BLOCK INTERVAL (with Start Demand Interval Logic Trigger)
This method calculates a linear average of the quantity (RMS current, real power, reactive power, or apparent power) over
the interval between successive Start Demand Interval logic input pulses. Each new value of demand becomes available at
the end of each pulse. Assign a FlexLogic operand to the
5
demand interval pulses.
If no trigger is assigned in the
culating method #2. If a trigger is assigned, the maximum allowed time between 2 trigger signals is 60 minutes. If
NOTE
no trigger signal appears within 60 minutes, demand calculations are performed and available and the algorithm
resets and starts the new cycle of calculations. The minimum required time for trigger contact closure is 20 μs.
CALCULATION METHOD 3: ROLLING DEMAND
This method calculates a linear average of the quantity (RMS current, real power, reactive power, or apparent power) over
the programmed demand time interval, in the same way as Block Interval. The value is updated every minute and indicates
the demand over the time interval just preceding the time of update.
a) MAIN MENU
PATH: SETTINGS
PRODUCT SETUP
 USER-PROGRAMMABLE
 LEDS
5-76
Figure 5–9: THERMAL DEMAND CHARACTERISTIC
DEMAND TRIGGER


USER-PROGRAMMABLE LEDS

 LED TEST
 TRIP & ALARM LEDS
MESSAGE
 USER-PROGRAMMABLE
MESSAGE
 LED 1
 USER-PROGRAMMABLE
MESSAGE
 LED 2
 USER-PROGRAMMABLE
MESSAGE
 LED 48
F35 Multiple Feeder Protection System
Time (minutes)
setting to program the input for the new
DEMAND TRIGGER
setting and the
CRNT DEMAND METHOD
5.2.11 USER-PROGRAMMABLE LEDS
See below
See page 5–79.
See page 5–79.
5 SETTINGS
842787A1.CDR
is "Block Interval", use cal-
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents