5.6 GROUPED ELEMENTS
The undervoltage delay setting defines the family of curves shown below.
where: T = operating time
D = undervoltage delay setting (D = 0.00 operates instantaneously)
V = secondary voltage applied to the relay
V
= pickup level
pickup
5
At 0% of pickup, the operating time equals the UNDERVOLTAGE DELAY setting.
NOTE
5-164
D
T
--------------------------------- -
=
V
1
------------------
V
pickup
% of voltage pickup
Figure 5–64: INVERSE TIME UNDERVOLTAGE CURVES
F35 Multiple Feeder Protection System
842788A1.CDR
5 SETTINGS
(EQ 5.21)