Data Records And Functions - Siemens Simantic ET200SP System Manual

Table of Contents

Advertisement

Configuration control (option handling)
9.2 Creating the control data record
Error messages
In case of error, the RDREC instruction returns the following error messages via the
STATUS block parameter while reading the feedback data record:
Table 9- 8
Error code
80B1
80B5
80B8
9.2.5

Data records and functions

Supported data records and functions
The table below shows a comparison of the supported data records and functions depending
on the CPU/interface module used.
Supported data rec-
ords and functions
Control data record
(V2)
Simplified control data
record (V1)
Read back control data
record *
Read feedback data
record
* You can read back the control data record with the RDREC instruction.
186
Error messages
H
H
H
CPU...
1510SP-1 PN
1512SP-1 PN
1510SP F-1 PN
1512SP F-1 PN
--
--
--
--
Meaning
Invalid length; the length information in data record 197 is not
correct.
Configuration control not configured
Parameter error
The following events cause a parameter error:
Incorrect block ID in the header (not equal to 197)
Invalid version identifier in the header
A reserved bit has been set
The same slot in the station option has been assigned to more
than one slot in the station master
Interface module (IM...)
155-6 PN
155-6 PN
HS
HF
155-6 PN
155-6 PN
ST
BA
Distributed I/O system
System Manual, 12/2016, A5E03576849-AG
155-6 DP
HF
--

Hide quick links: