Commissioning
10.2 Commissioning the ET 200SP for PROFINET IO
Commissioning procedure
To commission the ET 200SP distributed I/O system CPU as an IO controller for
PROFINET IO, we recommend the following procedure:
Table 10- 1
Step
1
2
3
4
5
6
7
8
9
10
The IO devices are configured with the IO controller.
1
200
Procedure for commissioning the ET 200SP CPU as an IO controller for PROFINET IO
Procedure
Installing ET 200SP
Connecting ET 200SP
Supply voltages
PROFINET IO
Sensors and actuators
Inserting a SIMATIC memory card in the IO con-
troller
Configuring the IO controller
Switching on supply voltages for the IO controller
Switching on supply voltages for IO devices
Downloading the configuration to the IO controller STEP 7 online help
Switching IO controller to RUN mode
Checking LEDs
Testing inputs and outputs
See ...
Section Installation (Page 54)
Section Wiring (Page 75)
Section Removing/inserting a
SIMATIC memory card on the CPU
(Page 209)
Section Configuring (Page 140)
1
CPU 15xxSP-1 PN
(http://support.automation.siemens
.com/WW/view/en/90466439/1333
00) manual
Documentation of the IO device
CPU 15xxSP-1 PN
(http://support.automation.siemens
.com/WW/view/en/90466439/1333
00) manual
CPU 15xxSP-1 PN
(http://support.automation.siemens
.com/WW/view/en/90466439/1333
00) manual
The following functions are helpful:
Monitoring and modifying tags,
testing with program status, forc-
ing, controlling the outputs. See
section Test functions and elimi-
nating problems (Page 259)
System Manual, 12/2016, A5E03576849-AG
Distributed I/O system