Commissioning procedure
To commission the ET 200SP distributed I/O system as a DP master on PROFIBUS DP, we
recommend the following procedure:
Table 10- 4
Step
1
2
3
4
5
6
7
8
9
10
Distributed I/O system
System Manual, 12/2016, A5E03576849-AG
Procedure for commissioning the ET 200SP as a DP master on the PROFIBUS DP
Procedure
Installing ET 200SP (with CPU and CM DP)
Connecting ET 200SP
Supply voltages
PROFIBUS DP
Sensors and actuators
Inserting a SIMATIC memory card in the DP
master (CPU)
Configuring DP master (including PROFIBUS
address)
Switching on supply voltages for DP master
Switching on supply voltages for DP slaves
Download configuration to the DP master
Switching DP master to RUN
Checking LEDs
Testing inputs and outputs
10.3 Commissioning the ET 200SP on PROFIBUS DP
See ...
Section Installation (Page 54)
Section Wiring (Page 75)
Section Removing/inserting a
SIMATIC memory card on the CPU
(Page 209)
CPU 15xxSP-1 PN
(http://support.automation.siemens
.com/WW/view/en/90466439/1333
00) and CM DP manual
CPU 15xxSP-1 PN
(http://support.automation.siemens
.com/WW/view/en/90466439/1333
00) manual
Documentation of the DP slave
STEP 7 online help
CPU 15xxSP-1 PN
(http://support.automation.siemens
.com/WW/view/en/90466439/1333
00) manual
CPU 15xxSP-1 PN
(http://support.automation.siemens
.com/WW/view/en/90466439/1333
00) manual
The following functions are helpful:
Monitoring and modifying tags,
testing with program status, forc-
ing, controlling the outputs. See
section Test functions and elimi-
nating problems (Page 259)
Commissioning
205