Connecting The Expansion Vessel; Connecting The Condensate Discharge Pipe - DeDietrich IX 245-130 Installation, User And Service Manual

Floor-standing condensing gas boiler
Table of Contents

Advertisement

7 Installation
Fig.72
Tab.26
Volume of the expansion vessel depending on the volume of the installation
Initial pressure of
the expansion ves­
100
sel
50 kPa
4.8
(0.5 bar)
100 kPa
8.0
(1 bar)
150 kPa
13.3
(1.5 bar)
Fig.73
2
60
IX
5
MW-5000810-2
125
150
6.0
7.2
10.0
12.0
16.6
20.0
1
5. Fit the circulating pump on the heating return pipe (circulating pump
not provided).
7.3.2

Connecting the expansion vessel

1. Determine the volume of the expansion vessel depending on the
volume of the installation.
2. Connect the expansion vessel to the heating circuit return pipe.
Volume of the expansion vessel for the installation
Volume of the installation (in litres)
175
200
250
8.4
9.6
12.0
14.0
16.0
20.0
23.3
26.6
33.3
Terms and conditions of validity:
Safety valve calibrated to 0.6 MPa (6 bar).
Average water temperature: 70°C.
Heating circuit flow temperature: 80°C.
Heating circuit return temperature: 60°C.
Filling pressure in the system lower than or equal to the initial pressure
in the expansion vessel.
7.3.3

Connecting the condensate discharge pipe

The condensate discharge pipe is located inside the boiler.
Do not block the condensate discharge pipe.
Set the discharge pipe at a gradient of at least 30 mm per metre,
maximum horizontal length 5 metres.
Do not drain condensation water into a roof gutter.
Connect the condensate discharge pipe in accordance with prevailing
standards.
It is preferable to use the condensate neutralisers recommended by the
manufacturer of the boiler.
1. Connect a plastic hose to the condensate discharge outlet (DN18) or
a rigid pipe (DN32).
2. Insert the other end of the hose into a waste water discharge outlet.
Important
Treat the condensate in accordance with prevailing local
regulations.
300
> 300
14.4
Volume of the installation x
0.048
24.0
Volume of the installation x
0.080
39.9
Volume of the installation x
0.133
7702684 - v04 - 05092019