Technical data
11.1
Technical specifications
Technical specifications for MAG 6000 I standard and Ex version
Mode of operation and design
Input
Output
Low flow cut off
Galvanic isolation
Max. measuring error
(incl. sensor and zero point)
Rated operation conditions
MAG 6000 I / MAG 6000 I Ex de transmitter
Operating Instructions, 04/2016, A5E02083319-AG
Measuring principle
Empty pipe
Excitation frequency
Electrode input impedance
Digital input
Activation time
Current
Current output
Signal range
Active current output
Passive current output
Time constant
Digital output
Frequency
Time constant
Pulse (passive)
Time constant
Relay output
Time constant
Load
0 ... 9.9% of maximum flow
All inputs and outputs are galvanically isolated PELV circuits with 60 VDC isolation
from each other and ground. Exceptions are sensor connections that are connected
to ground.
MAG 6000 I/MAG 6000 I Ex de
Ambient temperature
Electromagnetic with pulsed constant field
Detection of empty pipe (special cable re-
quired in remote mounted installation)
Depends on sensor size
> 1 x 10
Ω
14
11 to 30 V DC, R
= 4.4 kΩ
i
50 ms
I
= 2.5 mA, I
= 7 mA
11 V DC
30 V DC
0 to 20 mA (active/passive)
R
500 Ω @ V
30 V DC
max
max
R
0 Ω @ V
12 V DC
min
min
R
500 Ω @ V
30 V DC
max
max
0.1 to 30 s, adjustable
0 to 10 kHz, 50% duty cycle
(uni/bidirectional)
0.1 to 30 s, adjustable
3 to 30 V DC, max. 110 mA (Ex version:
max. 30 mA), 200 Ω ≤ R
i
from connected equipment)
0.1 to 30 s, adjustable
Changeover relay, same as current output
30 VAC/2 A, 24 VDC/1 A
±0.2% ± 1 mm/s
1)
11
≤10 kΩ (powered
61