Wire insulation
The insulation between the connected mains supply and 24 V AC/DC supply for the
flowmeter must at least be rated with double or reinforced insulation at mains voltage.
Cable glands
For Ex zone 1 installations only certified cable glands with protection type "e" can be used
for the power supply and the coil cable. The cable glands must be approved for the actual
temperature and cable dimension.
MAG 6000 I / MAG 6000 I Ex de transmitter
Operating Instructions, 04/2016, A5E02083319-AG
WARNING
WARNING
Technical data
11.6 Cable requirements