Siemens SITRANS F MAG 6000 I Operating Instructions Manual page 16

Electromagnetic flowmeters
Hide thumbs Also See for SITRANS F MAG 6000 I:
Table of Contents

Advertisement

Safety notes
2.3 Installation in hazardous area
Compact transmitter version:
● Ex d e [ia] ia IIC T3-T6 Gb
Ex tD A21 IP67 T** °C (** pipe temperature +5K, but not less than T85 °C
(MAG 3100 / MAG 3100 P)
● Ex d e [ia] ia IIB T3-T6 Gb
Ex tD A21 IP67 T** °C (** pipe temperature +18K, but not less than T85 °C
(MAG 1100 / MAG 1100 F)
For sensors:
Refer to sensor certificates:
MAG 3100 / MAG 3100 P: Sira 07ATEX1182X (DN 15-DN300); Sira 03ATEX3339X (DN350-
DN2000)
MAG 1100 / MAG 1100 F: Sira 07ATEX3181X
Safety parameters associated with the remote transmitter version
Table 2- 1
Sensor electrode input (Terminals 0, 81, 82, 83, 84 - "ia circuits")
U
O
I
O
C
O
L
O
P
O
Sensor coil terminals
85 and 86
Power supply:
Parameter
Supply
Max. allowable supply voltage U
ATEX certificate)
Ambient temperature
Enclosure
14
Intrinsically safe data
IIB
30 V DC
6.1 mA
560 nF
1 H
45.5 mW
(according to
m
IIC
30 V DC
6.1 mA
66 nF
0.96 H
45.5 mW
Terminal type
"e"
MAG 6000 I Ex de
115 to 230 VAC or 18 to 30 VDC
264 V
-20 to +60 °C (-4 to 140 °F)
IP67 / NEMA 4X
MAG 6000 I / MAG 6000 I Ex de transmitter
Operating Instructions, 04/2016, A5E02083319-AG