● Remove cover for connection board.
● Remove protection plate for connectors
● Remove the two connectors.
● Mount the two cables through the two cable glands and mount connectors on coil and
electrode cables.
● Mount the two connectors on connection board; fit protection plate and fasten bolt.
1. Tighten all cable glands on sensor and transmitter to obtain optimum sealing.
2. Mount cover for connection board and mount lid on sensor.
3. Transmitter is ready to be powered up.
MAG 6000 I / MAG 6000 I Ex de transmitter
Operating Instructions, 04/2016, A5E02083319-AG
NOTICE
Exposing the transmitter to direct sunlight may increase the operating temperature
above its specified limit, and decrease display visibility.
In such case, protect the transmitter from direct sunlight.
5.3 Connection of sensor and transmitter in remote version
Connecting
35