CHAPTER 5: SETTINGS
The C30 is provided with this optional feature, specified as an option at the time of ordering. Using the order
code for your device, see the order codes in chapter 2 for details.
The figure shows a general form of a PID regulator in the s domain.
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
PID 1 SAMPLE TIME:
0.05 s
PID 1 PROCESS
SIGNAL: Off
PID 1 SETPOINT
SIGNAL: 0.00
PID 1 TRACKING SIGNAL:
Off
PID 1 PROPORTIONAL
GAIN: 1.00
PID 1 SETPOINT
WEIGHTING: 1.00
PID 1 INTEG. TIME
CONST.: 1.00 sec
PID 1 ANTIWINDUP:
Disabled
PID 1 AW TIME CONST.:
1.00 sec
PID 1 DERIV. TIME
CONST.: 1.00 s
PID 1 DERIVATIVE
LIMIT: 10
PID 1 MAX:
10
PID 1 MIN:
10
PID 1 Tmin:
500 ms
PID 1 DEAD TIME:
1.00 sec
PID 1 BLK:
Off
PID 1
TARGET: Self-reset
PID 1
EVENTS: Disabled
Range: 0.05 to 30.00 s in steps of 0.01
Range: Off, any FlexAnalog parameter
Range: -99999.99 to 99999.99 in steps of 0.01
Range: Off, any FlexAnalog parameter
Range: 0.01 to 100.00 in steps of 0.01
Range: 0.01 to 1.00 in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
Range: Enabled, Disabled
Range: 0.00 to 600.00 s in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
Range: 1 to 20 in steps of 1
Range: -10000 to 10000 in steps of 1
Range: -10000 to 10000 in steps of 1
Range: 100 to 1000 ms in steps of 1
Range: 1 to 20 s in steps of 1
Range: FlexLogic operand
Range: Self-reset, Latched, Disabled
Range: Enabled, Disabled
CONTROL ELEMENTS
5
5-161