GE C30 Instruction Manual page 28

Controller system
Hide thumbs Also See for C30:
Table of Contents

Advertisement

SIGNAL PROCESSING
2
The UR samples its AC signals at 64 samples per cycle, that is, at 3840 Hz in 60 Hz systems, and 3200 Hz in 50 Hz systems.
The sampling rate is dynamically adjusted to the actual system frequency by an accurate and fast frequency tracking
system.
The A/D converter has the following ranges of AC signals:
Voltages:
Currents:
Current harmonics are estimated based on raw samples with the use of the full-cycle Fourier filter. Harmonics 2nd through
25th are estimated.
2-16
Figure 2-2: UR signal processing
CHAPTER 2: PRODUCT DESCRIPTION
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
Eq. 2-1
Eq. 2-2

Advertisement

Table of Contents
loading

Table of Contents