GE C30 Instruction Manual page 121

Controller system
Hide thumbs Also See for C30:
Table of Contents

Advertisement

CHAPTER 4: INTERFACES
The status indicators in the first column are as follows:
IN SERVICE — This LED indicates that control power is applied, all monitored inputs, outputs, and internal systems are
OK, and that the device has been programmed
TROUBLE — This LED indicates that the relay has detected an internal problem
TEST MODE — This LED indicates that the relay is in test mode. For more information, see the Test Mode section in the
Settings chapter.
TRIP — This LED indicates that the FlexLogic operand serving as a trip switch has operated. This indicator always
latches; as such, a reset command must be initiated to allow the latch to reset.
ALARM — This LED indicates that the FlexLogic operand serving as an alarm switch has operated. This indicator is
never latched.
PICKUP — This LED indicates that an element is picked up. This indicator is never latched.
The event-cause indicators in the first column are as follows.
Event-cause LEDs are turned on or off by protection elements that have their respective target setting selected as either
"Enabled" or "Latched." If a protection element target setting is "Enabled," then the corresponding event-cause LEDs
remain on as long as the operate operand associated with the element remains asserted. If a protection element target
setting is "Latched," then the corresponding event-cause LEDs turn on when the operate operand associated with the
element is asserted and remain on until the
All elements that are able to discriminate faulted phases can independently turn off or on the phase A, B, or C LEDs. This
includes phase instantaneous overcurrent, phase undervoltage, and so on. This means that the phase A, B, and C operate
operands for individual protection elements are ORed to turn on or off the phase A, B, or C LEDs.
VOLTAGE — This LED indicates voltage was involved
CURRENT — This LED indicates current was involved
FREQUENCY — This LED indicates frequency was involved
OTHER — This LED indicates a composite function was involved
PHASE A — This LED indicates phase A was involved
PHASE B — This LED indicates phase B was involved
PHASE C — This LED indicates phase C was involved
NEUTRAL/GROUND — This LED indicates that neutral or ground was involved
In the C30, only the OTHER indicator is applicable and indicates that a digital element was involved.
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
Figure 4-23: Typical LED panel for enhanced faceplate
button on the front panel is pressed after the operand is reset.
RESET
FRONT PANEL INTERFACE
4-21
4

Advertisement

Table of Contents
loading