Always confirm contact operation prior to wiring.
From
UPS 1 CAN Bridge Card J3-1 (Alarm)
UPS 1 CAN Bridge Card J3-2 (Alarm
Return)
UPS 1 TB2-1 (Pull Chain)
UPS 1 TB2-2 (Pull Chain Common)
UPS 2 CAN Bridge Card J3-1 (Alarm)
UPS 2 CAN Bridge Card J3-2 (Alarm
Return)
UPS 2 TB2-1 (Pull Chain)
UPS 2 TB2-2 (Pull Chain Common)
UPS 3 CAN Bridge Card J3-1 (Alarm)
UPS 3 CAN Bridge Card J3-2 (Alarm
Return)
UPS 3 TB2-1 (Pull Chain)
UPS 3 TB2-2 (Pull Chain Common)
UPS 4 CAN Bridge Card J3-1 (Alarm)
UPS 4 CAN Bridge Card J3-2 (Alarm
Return)
UPS 4 TB2-1 (Pull Chain)
MOB 1 Aux 2 COM
MOB 2 Aux 2 COM
MOB 3 Aux 2 COM
Table 5-4: Pull-Chain wiring terminations with MOBs
P-164000476
Revision 002
To
MOB 1 Aux 1 NC
MOB 1 Aux 1 Com
MOB 1 Aux 2 NO
UPS 2 TB2-2 (Pull Chain Common)
MOB 2 Aux 1 NC
MOB 2 Aux 1 Com
MOB 2 Aux 2 NO
UPS 3 TB2-2 (Pull Chain Common)
MOB 3 Aux 1 NC
MOB 3 Aux 1 Com
MOB 3 Aux 2 NO
UPS 4 TB2-2 (Pull Chain Common)
MOB 4 Aux 1 NC
MOB 4 Aux 1 Com
MOB 4 Aux 2 NO
MOB 2 Aux 2 Com
MOB 3 Aux 2 Com
MOB 4 Aux 2 Com
9395P 500kVA / 600 kVA
User's and Installation Guide
Function
MOB Open Alarm
Pull Chain
Pull Chain Common
MOB Open Alarm
Pull Chain
Pull Chain Common
MOB Open Alarm
Pull Chain
Pull Chain Common
MOB Open Alarm
Pull Chain
Pull Chain MOB Common