Table 35. Pull-Chain Wiring Terminations With Mobs - Eaton Power Xpert 9395 High Performance Installation And Operation Manual

Table of Contents

Advertisement

Installing Options and Accessories

Table 35. Pull-Chain Wiring Terminations with MOBs

From
UPS 1 CAN Bridge Card J3–1 (Alarm)
UPS 1 CAN Bridge Card J3–2 (Alarm Return)
UPS 1 TB2–1 (Pull Chain)
UPS 2 TB2–2 (Pull Chain Common)
UPS 2 CAN Bridge Card J3–1 (Alarm)
UPS 2 CAN Bridge Card J3–2 (Alarm Return)
UPS 2 TB2–1 (Pull Chain)
UPS 2 TB2–2 (Pull Chain Common)
UPS 3 CAN Bridge Card J3–1 (Alarm)
UPS 3 CAN Bridge Card J3–2 (Alarm Return)
UPS 3 TB2–1 (Pull Chain)
UPS 3 TB2–2 (Pull Chain Common)
UPS 4 CAN Bridge Card J3–1 (Alarm)
UPS 4 CAN Bridge Card J3–2 (Alarm Return)
UPS 4 TB2–1 (Pull Chain)
MOB 1 Aux 2 Com
MOB 2 Aux 2 Com
MOB 3 Aux 2 Com
5 5 . . 3 3
I I n n s s t t a a l l l l i i n n g g a a n n O O p p t t i i o o n n a a l l R R e e m m o o t t e e M M o o n n i i t t o o r r P P a a n n e e l l I I I I
To install RMP II wiring:
1.
Verify the UPS system is turned off and all power sources are removed. See for shutdown instructions
Chapter 7 UPS Operating
2.
Perform the procedure listed in paragraph
NOTE
3.
Securely mount the RMP II at the desired location. See
NOTE
112
Eaton
®
Instructions.
If mounting to a hollow wall, secure the enclosure to a wood or metal stud within the
wall. Do not use hollow wall anchors.
When installing signal wiring for CAN card J3 terminals, conduit must be installed
between the device and the UPS cabinet.
Power Xpert
®
9395P-900 Installation and Operation Manual 164000501—Rev 12
To
MOB 1 Aux 1 NC
MOB 1 Aux 1 Com
MOB 1 Aux 2 NO
UPS 2 TB2–2 (Pull Chain Common)
MOB 2 Aux 1 NC
MOB 2 Aux 1 Com
MOB 2 Aux 2 NO
UPS 3 TB2–2 (Pull Chain Common)
MOB 3 Aux 1 NC
MOB 3 Aux 1 Com
MOB 3 Aux 2 NO
UPS 4 TB2–2 (Pull Chain Common)
MOB 4 Aux 1 NC
MOB 4 Aux 1 Com
MOB 4 Aux 2 NO
MOB 2 Aux 2 Com
MOB 3 Aux 2 Com
MOB 4 Aux 2 Com
5.1 Installing an Optional Hot Sync CAN Bridge
Figure 65
for mounting hole locations.
Function
MOB Open Alarm
Pull Chain
Pull Chain Common
MOB Open Alarm
Pull Chain
Pull Chain Common
MOB Open Alarm
Pull Chain
Pull Chain Common
MOB Open Alarm
Pull Chain
Pull Chain MOB Common
Card.

Advertisement

Table of Contents
loading

This manual is also suitable for:

9395p-900

Table of Contents