Multi-Idrive Installation With Regenerative Loads - IMO iDrive EDX 100V series 1-ph/0.2 – 0.75kW (0.25 – 1HP) Owner's Manual

Ac micro-inverters for small 3-phase induction motors
Table of Contents

Advertisement

3.8 Multi-iDrive installation with regenerative loads

Built in
braking
resistor
If all iDrives are of the same voltage rating, the DC bus connections of each can be
connected together in parallel. Regenerated braking power from stopping of high inertia
loads can then be dissipated or partly dissipated between all of the paralleled iDrives.
If more energy requires dissipating, a braking module and resistors can be connected as
shown above.
Note: All drives must power on at the same time*.
Notes:
*If parallel connecting the DC busses of different capacity inverters;
Must power up in sequence: Largest capacity first → smallest capacity last.
DC fuses and/or other precautions may be necessary.
Never connect '+' terminals to '–' terminals or damage will occur.
If in doubt consult your local iDrive distributor or dealer.
Chapter 3 Environment description and installation
3-25
DC link parallel
connections
+ → + → + → +
-
-
-
-