1.) When the acceleration time is set too short the iDrive may trip on Over-Current (OC).
If the time accelerating time cannot be increased use stall-prevention. A stall-prevention level
needs to be programmed and when the inverter detects this level it freezes the acceleration
ramp until the current falls below the set level, then continues accelerating.
2.) When the Deceleration time is set too short the iDrive may trip on Over-Voltage (OU).
If the time deceleration time cannot be increased then stall-prevention can be used. A stall-
prevention level has to be programmed and when the inverter detects this level it holds the
deceleration ramp until the DC link voltage falls below the factory set level, then continues
decelerating.
3.) The iDrive could stall during run mode due to an impact load or sudden changes of the load.
Stall prevention in run mode will detect a programmed stall level (b25) for a period of time
(b30) , if the level exceeds b25 , then the iDrive reduces its output frequency (speed) to
provide the required additional torque to overcome the stall condition. Once this level is
below the programmed stall level then it ramps up to its normal running speed.
b31 Auto restart on momentary power loss. 000: Enabled
b31 = 000: Auto restart after a momentary power loss is enabled on resumption of power and
application of run signal, according to setting of parameter A00.
The iDrive will carry out an auto speed search, once the motor speed and direction are found then it
will accelerate to the running speed prior to the power loss.
b31 = 001: Auto restart disabled.
b32 Auto restart times: 000 ~ 005
1.) b32 = 000: The iDrive will not auto-restart on fault trip.
2.) b32 > 000
The iDrive will carry out an auto-speed search 0.5 sec after the fault trip, while the output
is switched off and the motor is coasting to stop.
Once the rotating speed is determined the iDrive will accelerate or decelerate from this speed to the
running speed before the fault.
3.) Auto restart will not occur following OL1, OL2, OH, or BB alarms.
Note:- Auto restart will not function while DC injection braking or decelerating to stop.
b33 Auto-start on power up
Danger:
1.) When b33 = 000 and external run mode (A00 = 001) are selected and a RUN command is
present, the iDrive will auto-start the motor when power is applied.
This feature should only be considered when all safety implications of its use have been
investigate, risk assessment for maintenance, use of warning labels etc.
2.) When b33 = 001 and external run mode (A00 = 001) are selected, and a RUN command is
present, the motor will not auto-start when power is applied to the iDrive .
The iDrive display will flash and SP1' error message. It can only restart after the RUN
command has been removed then reapplied.
001: Disabled
000: Enable direct start on power up.
001: Disable direct start on power up.