IMO iDrive EDX 100V series 1-ph/0.2 – 0.75kW (0.25 – 1HP) Owner's Manual page 30

Ac micro-inverters for small 3-phase induction motors
Table of Contents

Advertisement

Control signal terminal block description
1 2 3
TM2
Terminal
RA
Multi-functional output terminals.
Normally open relay contacts SPST
RB
10V
+10Vdc terminal. Supply for external potentiometer for speed reference.
Analog frequency command input or PID feedback signal terminal.
AIN
(Refer to parameter b41)
24Vdc common terminal; Frame size 1 maximum current = 100mA
24V
PNP (SOURCE) for inputs S1~S4 (and option card inputs S5 and S6).
Set SW1 to 'PNP' position. Connect option card power supply if required.
0Vdc common terminal.
NPN (SINK) for input, S1~S4 (and option card inputs S5 and S6).
COM
Set SW1 to 'NPN' position. Connect option card power if required.
Also use this terminal for analogue input and analogue output signals - common.
Multi-function analog output terminal, (refer to parameter b53 for functions)
Output signal: 0-10Vdc proportional to b53 setting.
FM+
Maximum output current = 25mA
Terminal
S1
Multi-function input terminals (refer to parameters b35~b38 descriptions)
S2
Maximum input current per terminal: Frame size 1 = 20mA.
S3
S4
Chapter 3 Environment description and installation
4
5 6
7 8 9 10 11 12
Description
Frame size 2 maximum current = 150mA
Description
3-20
Rated contact capacity:
(250VAC/10A resistive)
(Refer to parameter b55 for functions)
Frame size 2 = 25mA

Advertisement

Table of Contents
loading

Table of Contents