IMO iDrive EDX 100V series 1-ph/0.2 – 0.75kW (0.25 – 1HP) Owner's Manual page 49

Ac micro-inverters for small 3-phase induction motors
Table of Contents

Advertisement

• When the motor output torque is not enough, increase b14 set value.
• If the motor vibrates or becomes very hot decrease b14 set value.
• If running at low speeds for long periods, high b14 set value can cause the motor to overheat
• The maximum output torque limit is proportional to the iDrive rated current.
• If increasing b14 set value causes the output current to be too large, increase b03 set value.
b15 Slip Compensation Gain (Only for V/F control, A06 = 001)
If the detected motor load is too large, speed will drop. Increase gain b15 to compensate.
F
I
=
Δ
slip
(load current) (slip compensation )
• Torque/Speed curve pattern:
C %
B %
A %
• Operating frequency range: 0 ~motor rated frequency.
• When the motor load is high, speed will decrease (slip). Increase b15 set value to compensate.
• If the motor vibrates or becomes very hot decrease b14 set value.
• The maximum rotational output speed limit is fixed by the motor maximum set frequency.
b16 Low Frequency DB Voltage Compensation (Only for V/F control, A06 = 001)
Increasing b16 set value will increase output voltage and low frequency torque.
• Output voltage/frequency pattern:
V
6
b1
• Operating frequency range:
• At low operating frequency: -
When the motor output torque is not enough increase b16 set value.
Gain
F
Δ
slip
Q
0~10HZ / 50HZ
0~12HZ / 60HZ
4-14
RPM
F
Chapter 4 Software index

Advertisement

Table of Contents
loading

Table of Contents