Alarm Panel Indicators; Check The Fans; Verify Remote Interface; Connect Jetcraft Pc To Cpx-1000 - Paradyne Jetstream CPX-1000 Installation And Operation Manual

Voice services platform
Hide thumbs Also See for Jetstream CPX-1000:
Table of Contents

Advertisement

3. Installing the CPX-1000
Step 9
Step 10
Alarm Panel
Indicators
Step 1
Step 2

Check the Fans

Step 1
Step 2
Verify Remote
Interface
Connect JetCraft
PC to CPX-1000
Change CPX
Default IP
Address
3-34
Echo Cancellation Indicators: Verify that the Hot Swap
indicator is not lit. The STATUS indicator lights yellow when the
CPX is using the module.
Echo Cancellation and Compression Module Indicators:
Verify that the Hot Swap indicator is not lit. The STATUS indicator
lights yellow when the CPX is using the module.
Check the Alarm panel indicators:
Verify that the
indicator flashes on and off continuously
APP
(one second on, one second off).
Verify that all of the system status indicators are off (they are
not used).
The two CPX Power Supply Fan modules are equipped with an
integral fan assembly, and a third fan is supplied for redundancy
(in case one of the other two fans fails).
When power is first applied, the fans should run continuously,
circulating air through the system's plug-in modules.
Verify that the fans are running, and that the front vents on the
power supplies and the shelf rear vents are free of obstruction.
The CPX requires a remote connection for remote management. To
verify the remote port operation after powering up the CPX,
perform these tasks:
Make sure that JetCraft is installed on a PC. Connect the PC
directly to the ETHERNET 1 port on the MP transition card.
For this connection, use a CAT-5 crossover cable with RJ-45 plugs.
The default IP address for the CPX is:
IP address
subnet mask
10.0.10.100
255.255.0.0
1000-A2-GN22-00
February 2003